Chapter 3 Element Function
|
ScrEdit Software User Manual
3-26
Revision Apr. 30th, 2007, 2007PDD23000002
Property Description of Pipe (4) Element
Standard
Rotation 90
Rotation 180
Rotation 270
Style
Pipe Gauge
Use this option to set the pipe gauge. The selectable range is from 1 ~ 5. The setting
value 1 represents at least 13 pixels and the setting value 2 represents at least 26
pixels and vise versa.
Property Description of Pipe (5) Element
It is used to connect to several pipes. Pipe (5) element is shown as the figure below:
Standard
Rotation 90
Rotation 180
Rotation 270
Style
Pipe Gauge
Use this option to set the pipe gauge. The selectable range is from 1 ~ 5. The setting
value 1 represents at least 13 pixels and the setting value 2 represents at least 26
pixels and vise versa.
Property Description of Pipe (6) / Pipe (7) Element
Horizontal and vertical pipes. It is used to display the direction of water flow.
Read Address
The address can be internal memory or the controller address. (Please refer to Table
3.2.2 Property Description of General Buttons.)
The user can decide if the read address is set or not. If the read address is set, the
mobile cursor will display and move, just like the water flowing through the pipe. For
example, suppose that the internal memory address of HMI is $0, when $0 is 1, and
the mobile cursor color is set, the direction of water flow is from right to the left; when
$0 is 2, the direction of water flow is from left to the right. When $0 is set to other
value than 1 and 2, the water will not flow. In the same way, when the user select
Pipe (7) element, for example, suppose that the internal memory address of HMI is
$1, when $1 is 1, the direction of water flow is from bottom to the top; when $1 is 2,
the direction of water flow is from top to the bottom. When $1 is set to other value
than 1 and 2, the water will not flow.
Mobile Cursor Color
When there is any data occurred in the read address, the mobile cursor will display
and move, just like the water flowing through the pipe. The user can use this option
to set the mobile cursor color.
Pipe Gauge
Use this option to set the pipe gauge. The selectable range is from 1 ~ 5. The setting
value 1 represents at least 13 pixels and the setting value 2 represents at least 26
pixels and vise versa.
Summary of Contents for AE80THTD
Page 1: ......