eZV-440 Version 2.1 Application Guide
Page 60 of 67
Document Edition 2.5
Output Configuration Objects
Object Name
Object
Ref
Default
Units
Description
Options
Heat1FanMin
AV199
n/a
The optional interlock to increase
the minimum fan speed when Heat
1 stage is running.
Default = 0
Heat2FanMin
AV200
n/a
The optional interlock to increase
the minimum fan speed when Heat
2 stage is running.
Default = 0
Heat3FanMin
AV201
n/a
The optional interlock to increase
the minimum fan speed when Heat
3 stage is running.
Default = 0
Heat1
AV803
%
First heating stage
Default = 100
Heat2
AV804
%
Second heating stage
Default = 0
Heat3
AV805
%
Third heating stage
Default = 0
AirflowDemand
AV808
%
Airflow demand
Default = 100
Fan1
AV810
%
First fan stage.
Default = 0
DemandCtrlVent
AV813
%
Demand Control Ventilation. Its
value reflects the CO2 demand, and
can be used as an input to
ventilation dampers.
Default = 0
Custom1*
AV815
%
Custom stage associated with GCL
controlled output
Default = 0
Custom2*
AV816
%
Custom stage associated with GCL
controlled output
Default = 0
DamperCmd
AV832
%
Sets the damper position for the
VentilationDamper output.
Default = 0
OccIndicator
MV806
N/A
Used to display the occupancy icon
on the network sensor LCD screen.
Not Used, Off, On
Default = Not Used
*Available only with eZVP-440 programmable model