Configurable and Programmable enteliZONE Controllers
Page 18 of 84
eZFC-424R4-24 Application Guide
Edition 2.6
Click on a link below to find out more information about these programmable objects.
l
Fan Coil/ Heat Pump algorithm programmable objects
enOcean Integration (firmware 2.2 and higher)
Gateway Translation (GWT) and Gateway (GW) objects are available on the programmable
enteliZONE controllers so that you can integrate an enteliZONE programmable controller into an
enOcean wireless system using a CON-ENOC enOcean Gateway device.
For more information about how to configure the GWT objects, see the CON-ENOC Application
Guide on the CON-ENOC George Support
.
Upgrade to Fully Programmable Using Flash Loader (firmware 2.2 and higher)
Delta Controls Flash Loader (Version 3.40 R4) can be used to upgrade controllers from
configurable to fully programmable versions. Flash Loader is part of the ORCAview suite of
software.
Flash Loader connects to and upgrades 1 controller at a time over the BACnet Ethernet network.
This upgrade requires 3 Flash credits on a Flash Loader key. Go to the Flash Loader page
on the George Support web site for more information.
1. Insert a Flash Loader key with sufficient credits into a USB port on your workstation.
2. Download the .FLS upgrade file from the George Support web site onto your workstation.
Save the file in the Flash Loader folder that was created when you installed Flash Loader,
like C:\Program Files(x86)\ Delta Controls\3.40\Flash Loader.
3. Back up the controller database by saving it. Flash Loader does not save the database
before the upgrade.
4. Open Flash Loader version 3.40 R4 on your workstation.
5. In the Filename dropdown list, select the upgrade file on your workstation.
For example, for firmware 2.1, the file name will be eZONE R2.1 B-xxxxxx.fls, where xxxxxx
is the build number.
6. Click the Enables Features box to check it. The eZONE section is displayed.
7. Click the Settings button.
1. In the Protocol dropdown list, select BACnet Network.
2. In the Adapter dropdown list, select the Ethernet adapter that connects the
workstation to the controller network.
Summary of Contents for eZFC-424R4-24
Page 1: ...eZFC 424R4 24 Application Guide Edition 2 6...
Page 67: ...enteliZONE Sequence of Operations Page 66 of 84 eZFC 424R4 24 Application Guide Edition 2 6...
Page 70: ...eZFC 424R4 24 Application Guide Edition 2 6 Page 69 of 84...
Page 71: ...enteliZONE Sequence of Operations Page 70 of 84 eZFC 424R4 24 Application Guide Edition 2 6...