Expert
Logger
Selection
Description
Trigger block
end
End of a trigger block (data storage).
Input value
outside the
(permissible)
range
The source channel value cannot be processed, there is a
parameter error. Check the parameters specified.
Recursion
When a channel is used for a calculation and the input sig-
nal of that channel depends on the calculation, there is a
loop and thus a recursion. The
Meti
OS
software recog-
nises this; the calculation is terminated and this status is
set.
Overload
An analogue or digital input or output is overloaded. For
example, the power source for a Pt100 sensor may be
overloaded at one input. The load resistance could be too
small at one output, resulting in an excessive current.
4.11.23
Status monitoring
This software channel monitors the source and becomes active (switches
to " On" ) when the source assumes the specified status.
Refer also to
.
Available status functions and their meaning
Selection
Description
Wire break
Wire break in monitored channel.
Configuration
error
Error in monitored channel configuration.
Invalid value
Invalid value in monitored channel.
Measuring
range over-
run
The measured value is outside the (positive) measuring
range of the A/D converter, that is, it is too high in the pos-
itive range.
Measuring
range under-
run
The measured value is outside the (negative) measuring
range of the A/D converter, that is, it is too high in the neg-
ative range.
Hardware
error
Error in the hardware, please contact the service of
Del-
phin
.
Simulated
An internally generated value for testing, for example
166
Delphin Technology AG
Januar 2018
Expert
Logger
Manual