Version
Description
9.8(1.0)
Introduced on the Z9100-ON.
9.8(0.0P5)
Introduced on the S4048-ON.
9.8(0.0P2)
Introduced on the S3048-ON.
9.7(0.0)
Introduced on the S6000-ON.
9.2(1.0)
Introduced on the Z9500.
9.0.2.0
Introduced on the S6000.
8.3.19.0
Introduced on the S4820T.
8.3.11.1
Introduced on the Z9000.
8.3.7.0
Introduced on the S4810.
7.6.1.0
Introduced on the S-Series.
7.5.1.0
Introduced on the C-Series.
6.1.1.0
Introduced on the E-Series.
rmon hc-alarm
Set an alarm on any MIB object.
Syntax
rmon hc-alarm
number
variable
interval
{delta | absolute} rising-threshold
value
event-number
falling-threshold
value event-number
[owner
string
]
To disable the alarm, use the
no rmon hc-alarm
number
command.
Parameters
number
Enter the alarm integer number from 1 to 65535. The value must be unique in the RMON
alarm table.
variable
The MIB object to monitor. The variable must be in the SNMP OID format; for example,
1.3.6.1.2.1.1.3 The object type must be a 64-bit integer.
interval
Time, in seconds, the alarm monitors the MIB variables; this is the alarmSampleType in the
RMON alarm table. The range is from 5 to 3600 seconds.
delta
Enter the keyword
delta
to test the change between MIB variables. This is the
alarmSampleType in the RMON alarm table.
absolute
Enter the keyword
absolute
to test each MIB variable directly. This is the
alarmSampleType in the RMON alarm table.
rising-threshold
value event-number
Enter the keywords
rising-threshold
then the value (64 bit) the rising-threshold
alarm is either triggered or reset. Then enter the event-number to trigger when the rising
threshold exceeds its limit. This value is the same as the alarmRisingEventIndex or
alarmTable of the RMON MIB. If there is no corresponding rising-threshold event, the
value is zero.
Remote Monitoring (RMON)
1351