900010009
The node has the wrong drive ratio.
Description
An HDD or SSD has been replaced by a drive of the other type, which changed the configured ratio of SSD to HDD. This event
might be generated by a drive failure, which can also affect the configured ratio.
Administrator action
Determine the types of drives that are on the node by running the following command:
isi devices drive list
Any drives that are not functioning correctly will be flagged.
●
If the drives are incorrect, replace the drives with the correct types. You can download the latest version of drive
replacement guide from the Online Support site.
●
If the drives are correct, or if you need assistance obtaining the correct drive type, contact Technical Support.
900010010
The node has a 812 (3/4 chassis) SKU.
Description
This event is generated if the model number of the chassis is not properly updated after replacing a node chassis.
Administrator action
Contact Dell EMC PowerScale Technical Support to update the model number of the node.
900010011
The Baseboard Management Controller (BMC) or Chassis Management Controller (CMC) are unresponsive.
Administrator action
Gather logs, and then contact Technical Support for additional troubleshooting. For instructions on how to gather cluster logs,
see
.
900010012
A fuse might have failed in the node.
Description
If a fuse has failed, the suitcase must be replaced. Do not shut down the node until a replacement suitcase arrives.
120
Hardware events