AX100-Series - Installing a Fibre Channel Storage System with a Direct Connection to a Solaris Server
Connecting ac Power to an AX100 Storage System
Connecting ac Power to an AX100 Storage System
Read this section if you are connecting power to anAX100 (dual-SP)
storage system. If you are connecting power to an AX100SC
(single-SP) storage system, go to
Connecting ac Power to an AX100SC
Before You Start
To complete this procedure, you need
❑
The serial cable that shipped with the UPS. This cable allows
Navisphere Express to monitor UPS status. You may also need an
RJ45-DB9 adapter cable that shipped in the AX100-Series
accessory box to connect the UPS serial cable to the storage
system.
❑
The ac power cables appropriate to your power source. These
cables shipped with the storage system.
Connect the UPS Serial Cable to the AX100 Storage System
CAUTION
!
Be sure to use the unique serial cable supplied with your UPS; a
standard null-modem or other service serial cable may look
identical, but will not work. You may need to attach an adapter
cable to connect the UPS serial cable to the AX100 UPS port.
If the UPS serial cable has two DB9 connectors
:
1. Locate an RJ45-DB9 adapter cable in the AX100-Series accessory
box.
2. Plug the adapter cable into the UPS serial cable.
3. Plug the free end of the UPS serial cable into the serial port on the
UPS (Figure 13).
4. Plug the free end of the adapter cable into the UPS connector
(labeled with a +- battery icon) on SP A (Figure 13).