Applying PDU labels, VMAX 450F, VMAX 850F, VMAX 950F
Procedure
1. For each bay, locate and complete the PDU label.
Note
For three-phase power, enter data only in the P1 column.
2. Place the label on the top surface of the PDU enclosure for side A and B.
Figure 46 PDU label , single-phase and three-phase
Customer PDU Information
Power Zone B
PDU
Panel
CB(s)
P1 P2 P3
Power Zone A
PDU
Panel
CB(s)
P1 P2 P3
Figure 47 Label placement— Customer PDU Information
Rear View
Zone A PDU label
Zone B PDU label
Ground the cabinet
Equipment correctly installed within the cabinet is grounded through the AC power
cables and connectors. In general, supplemental grounding is not required.
If your site requires external grounding (for example, to a common grounding network
beneath the site floor), you can use the grounding lugs provided on each of the
cabinet’s bottom supports.
Best Practices for AC Power Connections