Verify the operation of a replacement part
Steps
1. From PowerStore Manager, select Hardware.
2. Select the appliance where you replaced the faulted part.
3. From the
Hardware
card, select the view of the system where the part was replaced.
The status of the replacement part should read
Healthy
. If the status is still
Faulted
, wait a few minutes and refresh PowerStore
Manager. If the status does not change, ensure that the part is correctly seated, or contact your service provider.
Replace a power/cooling module in a 25-drive
expansion enclosure
Take the following actions to remove the faulted power/cooling module from the 25-drive expansion enclosure and install a replacement
power/cooling module.
Identify a faulted part from PowerStore Manager
Before you replace a part, ensure that you have identified its location within the system. Using PowerStore Manager, you can identify and
locate a faulted part.
Steps
1. From PowerStore Manager, select Hardware.
2. Select the appliance that contains the faulted part.
3. From the
Hardware
card, select the view of the system where the faulted part is located.
Faulted parts appear in red in the image of the system, and report a status of
Faulted
in the State field.
Removing a faulted power/cooling module
Prerequisites
Identify the faulted power/cooling module by the amber fault LED.
Expansion enclosure service procedures