Configure System for Use
Topics:
•
Enable administrative communication
•
Accepting the End User License Agreement
•
•
Configuring additional system parameters
•
Configure HA for new installations
Enable administrative communication
For HA pairs, administrative communication must be enabled on both nodes.
The administrative interfaces are located on the management module on the rear of the chassis. These interfaces are for
management network traffic only. Do not use these interfaces for data traffic.
1. Connect an administrative console to the serial port on the back panel of the system.
2.
NOTE:
You must have 115200 baud rate for the DD9500 system to work properly; 9600 baud rate will not work for the
DD9500 system.
Launch a terminal emulation program from your computer and configure the following communication settings:
Table 27. Communications settings
Setting
Value
Baud rate
115200
Data bits
8
Stop bits
1
Parity
None
Flow control
None
Emulation
VT-100
3. Select
Enter
on your keyboard to activate the console.
NOTE:
If you do not see the prompt on your terminal to log in, then complete Step 4.
4. In the front of theDD9500 system, press the power button to power on the system. Check that the front blue power LED
(with the circle with a dot) also turns on.
5
80
Configure System for Use