Steps
1. Remove the 6.8 mm adapters and replace them with the appropriate hardware from the kit:
a. Using a flat-bladed screwdriver, remove the two 6.8 mm adapters from the adapter mounting block on the rails.
b. Select the correct adapters from the hardware kit and install the adapters into the adapter mounting block.
2. Locate the 4U rack space designated for the shelf.
3. Install the right rail to the rear channel.
a. Align the right rail so that the alignment pins are centered on the middle holes of the bottom two U spaces of the 4U
space.
b. Move the bracket with the alignment pins to their correct location.
c. Push the rail back to secure the rail posts in the cabinet channel.
An audible click indicates that the rail is secure in the channel. Make sure the rear post/catch mechanism is secure and
attached.
4. Install the right rail to the front channel.
a. Align the front of the right rail so that it is level and the front rail pins are aligned with the middle holes of the bottom two
U spaces of the 4U space.
b. Pull the rail forward, with the posts aligned with the middle holes of the bottom two U spaces of the 4U space.
An audible click indicates that the connection is secure.
5. Install the left rail by mirroring the previous steps.
6. Remove the shipping tape that is attached to the node rails.
L
R
Front
Rear
6
Tape
Figure 55. Removing shipping tape
7. On both left and right rail assemblies, install a single long screw between the rail posts in the center screw hole to secure the
rails as follows:
48
Install the Disk Shelves in the Rack