2. Lower the cooling fan assembly into the system until the cooling fan connectors engage with the connectors on the system
board.
3. Press the release levers to lock the cooling fan assembly into the system.
Figure 56. Installing the middle cooling fan assembly
Next steps
1. Follow the procedure listed in
After working inside your system
on page 67.
Flex bays
Removing a NVMe drive bay or flex bay
Prerequisites
NOTE:
The procedure to remove the flex bay is identical to removing the NVMe drive bay.
1. Follow the safety guidelines listed in
on page 66.
2. Follow the procedure listed in
Before working inside your system
3. Disconnect the slim optical-drive and the backplane cables.
4.
Remove the backplane from NVMe drive bay or the flex bay
Steps
1. Using the Phillips #2 screwdriver, remove the two screws that secure the NVMe drive bay to the system.
2. Push the release latch down and slide the NVMe drive bay out of the system.
Installing and removing system components
99