NOTE:
Do not remove the ear components from the failed chassis: integrated ear components and covers are provided
with the replacement chassis FRU.
3
Maintaining a level position, carefully slide the enclosure chassis from the rack.
4
Place the chassis on a static-protected work surface near the replacement enclosure chassis, with the removed disk drive modules
and screws.
Installing the replacement 2U storage enclosure in the
rack
This section provides the procedure for installing the replacement enclosure in its rack location.
NOTE:
•
See the ME4 Series Storage System Deployment Guide when installing the enclosure into the rack.
•
Install the enclosure into the rack before re-inserting the disk drive modules. Two people are required to move the enclosure.
1
Support the bottom of the enclosure chassis. Carefully lift/align the chassis and while maintaining a level position for the enclosure,
slide it into the rack.
2
Using the appropriate mounting hardware, secure the enclosure chassis to the rack.
3
Using the applicable retaining screws, secure the front and rear of the enclosure chassis to the rack and rails.
Module removal and replacement
79