2. Select
Save
to store the setting.
INFO
Remember to
Write
when you have finished editing the input/output configuration.
7.7.5 Configure the sensor setup
AI
AO
PWM
DI
DO
Configurable for:
●
Sensor setup overview
1. If applicable, select the analogue input function(s) on the
Functions
page.
2. On the
Sensor setup
page, configure a new curve for the sensor, or select a previously configured curve.
3. If applicable, create sensor failure alarms.
4.
Write
the sensor configuration to the controller.
Sensor setup: New curve
1. Select
Rename
to change the curve name.
•
2. Change the
Sensor output (x-axis)
units and range if necessary.
•
3. Change the
Function input (y-axis)
units and range if necessary.
•
•
INFO
PICUS deselects all the functions if you change the function input units.
4. Configure the points:
• Select
Add
to add a point.