9.
Sensor failure alarms
For sensor failure, you can
Enable
a
Below range alarm
and/or
Above
range alarm
. When the alarm is enabled, you can scroll down and configure
the alarm.
INFO
Be careful to give each sensor failure alarm a meaningful name.
Each sensor failure alarm is created as a configurable analogue alarm (one
of up to 200).
For each alarm, you can configure a set point based on the sensor output
units.
10.
Options
Save
* the changes temporarily.
CAUTION
The
Min
and
Max
sensor output and function input alone only do NOT create a straight line graph. You MUST
supply all the points required for the active area of the curve.
*Note:
Save
does not write the configuration to the controller. However, DEIF recommends that you save regularly if
you will configure several inputs and/or outputs before writing the configuration to the controller.
7.5.4 Alarms page
The
Alarms
page allows you to configure alarms for the selected analogue input.