6.3.8 Clear and reset the single-line diagram
1. To reset the single-line diagram, select
New
from the right side panel.
• The single-line diagram is cleared.
• The default diagram for the connected controller type is shown.
2. You can now redraw the single-line diagram as required.
6.3.9 Broadcast the single-line diagram
You must
Broadcast
the single-line configuration to
selected controller(s)
. This includes the controller you are
currently logged on and connected to.
INFO
Only controllers connected and logged on to from the
Connect
page are shown here.
CAUTION
PICUS allows you to broadcast to controller(s) even if they are not safe for commissioning. You must confirm this
override action and it is not automatic.
1. Select
Broadcast
, from the right side panel.
• You are prompted to select the controller(s) you wish to broadcast to:
•
•
indicates the controller is ready.
•
indicates the controller is not in switchboard mode, but can be overridden if required.
2. Select all the controllers you wish to broadcast the diagram to.
•
PPM 300 PICUS manual 4189341080 UK
www.deif.com
Page 67 of 213