11.Supervision
11.1 Introduction
11.1.1 Introduction
The supervision display allows you to view the current state of the entire system. You can control any of the different
controllers, that are connected together in the same system.
11.1.2 Busbar colours
Line
Colour
Notes
Black
Dead busbar (Voltage < 10 % of nominal voltage)
Grey
Not in operation
Green
Live busbar
Yellow
Unknown state
Red
Voltage present but is not within acceptable range.
11.1.3 Diagram icons
Icon
Colour
Notes
Dark grey box
Selected component.
Green dashed box
Associated component.
Red cross (X)
State of component unknown or component is not configured.
Up arrow / Down arrow
Indicates if the controller is activating the regulator (governor or
AVR) increase or decrease digital output.
The image is only visible if a governor and/or AVR relay output is
configured.
Status bar
Indicates the output percentage of the analogue output controlling
the regulator (governor or AVR). If the blue bar is not visible, it
indicates the output is at 0 %. If the blue bar is completely visible,
it indicates the output is at 100 %.
The image is only visible if a governor and/or AVR analogue
output is configured.
PPM 300 PICUS manual 4189341080 UK
www.deif.com