Enable CustomLogic
1. Go to
Configure > Parameters
.
2. Enable
CustomLogic
under
Utility > CustomLogic
.
3. Select
Write
from the right side panel.
9.6.2 Example 2: Basic inter-controller communication
Introduction
In this example CustomLogic is configured to activate and deactivate an external light every 5 seconds. The external light is
connected to controller 2, will flash when controller 1 is under switchboard control.
Logic restrictions
• The single line diagram must be the same on both controllers.
• CustomLogic must be activated on both controllers.
• There must be a network connection between both controllers.
Configure the output on controller 2
1. Go to
Configure > Input/output
.
2. Configure a digital output function for the light activation switch. (
Functions > CustomLogic > Outputs > CustomLogic
digital output
)
a. After configuration
CustomLogic digital output
changes to
Terminal(s) x, y, z, Slot #
, where x, y, z, and # represent
the terminal and hardware slot.