3.6 Safety
3.6.1 Checking the protection parameters
The designer should have configured all the necessary protections in each controller during the design phase. However,
different parts of the world and different owners can have different requirements for the AC protections.
It is therefore necessary to check all the protections against the list of protections required.. Ensure that for each required
protection:
• The nominal setting(s), which the protection is based on, are correct.
• The protection is enabled.
• The protection set point is correct.
• The protection time delay is correct.
• The action for the protection (for example,
Trip breaker
or
Warning
) is correct.
• The inhibit(s) (if present), which prevent the protection response, are correct.
To check the nominal settings and protections for each controller:
1. Connect to the controller using PICUS.
2. Under
Configure > Parameters
, you can find the nominal settings (see the example in the table below). Check that these
match the settings from the switchboard manufacturer.
3. Under
Configure > Parameters
, you can find the AC protections (see the example in the table below). Check the
parameters. Make changes as necessary.