background image

 

 
Dodge Engineering & Controls, Inc. 

Toll Free (877) 334-2875  Fax: (978) 244-1422 

 

Installation

 

EN221 and EN310 Non-Spring Return Electronic Actuators

 

EA0662R1

a

f

d

g

c

e

b

PUSH

 

 

Figure 1.  Parts of the EN221 and EN310 Actuators. 

a. Actuator 

b.  U-bolt shaft adapter 

c. Position 

indicator 

d.  Shaft adapter locking 

clip 

e. Position 

indicator 

adapter 

f. Mounting 

bracket 

g. Mounting 

screws 

 

Product Description 

This installation instruction describes the steps for 
direct-coupled mounting of the EN221 and EN310 
series non-spring return (NSR) electronic actuators.  

Product Numbers 

EN221x 

EN310x 

Installation Conventions 

WARNING: 

 

Personal injury or loss of life may 
occur if you do not follow the 
procedures as specified. 

CAUTION: 

 

Equipment damage or loss of 
data may occur if you do not 
follow procedure as specified. 

CLOCKWISE

COUNTER CLOCKWISE

EA0320R2

 

Required Tools 

• 

10 mm (13/32-inch) open-end wrench 

• 

Drill 

4 mm (5/32-inch) drill bit  

• 

Phillips screwdriver 

• 

Marker or pencil 

• 

Adjustable pliers 

Expected Installation Time 

30 minutes 

Prerequisite 

The actuator is shipped from the factory with a 5° 
pre-load to ensure tight close-off of the damper. To 
release the pre-load, press the 

PUSH

 button before 

mounting the actuator. 

Installation 

 

WARNING: 

Do not open the actuator.  

NOTE:

 

You must place the actuator on the 
damper shaft so that the front of the 
actuator is accessible. The label and the 
manual override button are on the front 
side.  

1.  Place the actuator on the damper shaft with the 

front of the actuator accessible. The label and 
the manual override button are on the front side.  

2. 

For the EN221B2x and EN310B2x only: 

Determine the rotation of the damper shaft. Set 
the direction of rotation arrow to match the 
rotation.  

 

Figure 2.  Direction of Rotation Switch. 

3. 

For all models: 

See Figure 3 and Figure 4 for 

clockwise-to-open (CW) installation. See Figure 
5 and Figure 6 for counterclockwise-to-open 
(CCW) installation. 

UL Doc. No. 129-272 

EAI/EN-1 

Dodge Engineering & Controls, Inc. 

Rev. 5, Jan., 2005

 

 

Summary of Contents for EN221

Page 1: ... Drill 4 mm 5 32 inch drill bit Phillips screwdriver Marker or pencil Adjustable pliers Expected Installation Time 30 minutes Prerequisite The actuator is shipped from the factory with a 5 pre load to ensure tight close off of the damper To release the pre load press the PUSH button before mounting the actuator Installation WARNING Do not open the actuator NOTE You must place the actuator on the d...

Page 2: ...be used in tandem applications NOTE EN310B2 containing offset and span features cannot be used in a tandem application PU SH 1 20mm 3 4 in 77 mm 3 in 77 mm 3 in 1 b LONGER SHAFTS SHORTER SHAFTS EA0870R1 a 2 3 4 3 2 a e b d d SHAFT ADAPTER ALIGNMENT MARK c c 5 4 PU SH PU SH PU SH 90 90 EA0355R1 1 2 3 4 EA0295R1 PU SH PU SH 3 4 Note Place the shaft adapter next to the alignment mark keeping the mark...

Page 3: ...adapter next to the alignment mark keeping the mark visible Figure 5 Shaft Adapter Placement for Counterclockwise Rotation on Short and Long Shafts Figure 6 Mount the Actuator to the Damper Shaft Figure 7 Attach the Mounting Bracket EA0356R1 1 2 EA0362R1 3 PU SH 4 4 3 PU SH EA0357R2 4 mm 5 32 in 2 PLACES 6 5 1 2 1 2 g f Place the actuator on the shaft with the damper blades in the desired 0 positi...

Page 4: ...e 9 PUSH Figure 9 3 Return the actuator gear train to the 0 position using the steps which follow for the clockwise or counterclockwise damper shaft rotation Clockwise to open a Insert the shaft adapter to the right as close as possible to the raised stop Figure 10 90 90 EA0674R1 PUSH Figure 10 b Hold down the PUSH button and rotate the shaft adapter to the left until it stops Figure 11 90 90 EA06...

Page 5: ...OTAT I O N Figure 13 6 Attach the clip 7 Rotate the damper blade shaft to its 0 position 8 Return the actuator to the damper shaft and tighten the shaft adapter to the damper shaft Mounting for NEMA 2 Rating 90 90 90 NEMA 2 EA1152R1 Figure 14 Acceptable NEMA 2 Mounting Position for Single and Tandem Applications Dual Auxiliary Switch S option A 5 0 10 20 30 70 80 90 0 10 20 30 70 80 90 B EA0413R2 ...

Page 6: ...start point can be adjusted between 0 to 5 VDC The span U can be adjusted between 2 to 30 VDC 100 0 UO U max 30 V YU v YS EA0411R1 2 5 10 35 2 1 3 Ys Mechanical positioning range 100 angle of rotation 90 Yu Control signal U0 Offset start point U Span Examples above Ex 1 U0 0V U 2V The minimum working range for Ys 100 Ex 2 U0 5V U 30V The maximum working range for Ys 100 Ex 3 U0 0V U 10V Factory se...

Page 7: ...rs are powered by one transformer CAUTION Do not parallel wire EN221 EN310 actuators with any other type of actuator including EN221 EN310 actuators with date codes earlier than 501 WARNING Mixed switch operation is not permitted to the switching outputs of both auxiliary switches A and B Either AC line voltage from the same phase must be applied to all six outputs of the dual auxiliary switches o...

Page 8: ...Switch A NC Gray blue S3 Switch A NO Gray pink S4 Switch B Common Black red S5 Switch B NC Black blue S6 Switch B NO Black pink Modulating Control 24 VAC M A B S1 S4 S2 S3 S5 S6 1 8 2 9 EA0284R1 Figure 22 Table 2 Modulating Control 24 VAC Color Standard Symbol Function Plenum 1 Red 2 Com Black 8 0 to 10 VDC input signal Gray 9 Output for 0 to 10 VDC position indication Pink S1 Switch A Common Gray...

Page 9: ... indicate an open circuit or no resistance c Apply a 24 VAC signal to wire 6 violet The DMM should indicate contact closure as the actuator shaft coupling reaches the setting of switch A d Stop applying a control signal to wire 6 violet e Connect wires S1 and S2 to the DMM The DMM should indicate an open circuit or no resistance f Apply a 24 VAC signal to wire 7 orange The DMM should indicate cont...

Page 10: ...ft coupling returns to the 0 position 7 Check auxiliary switch A S option a Set the DMM dial to OHMS resistance or continuity check b Connect wires S1 and S3 to the DMM The DMM should indicate an open circuit or no resistance c Apply a full scale input signal to wire 8 gray The DMM should indicate contact closure as the actuator shaft coupling reaches the setting of switch A d Connect wires S1 and...

Page 11: ...4 in 7 mm min 8 in 200 mm 3 3 8 in 86 mm 1 1 8 in 28 mm 7 3 4 in 197 mm 11 in 279 mm 3 15 16 in 100 mm 1 23 32 in 30 mm 2 1 4 in 57 mm 25 32 in 20 mm EA0249R2 9 in 230 mm min 4 in 100 mm PL0132R1 10 mm 11 32 in OPENING FOR 3 8 FLEX CONDUIT 3 PLS 1 1 in 28 5 mm Figure 23 Dimensions of the EN221 and EN310 Actuator and Mounting Bracket UL Doc No 129 272 EAI EN 11 Dodge Engineering Controls Inc Rev 5 ...

Page 12: ...nches Millimeters 95 1 11 32 34 mm 1 11 32 34 mm min 1 4 in 7 mm min 1 4 in 7mm 1 11 32 34 mm 1 11 32 34 mm min 2 1 2 in 60 mm min 8 in 200 mm 7 3 4 in 197 mm 11 in 279 mm 3 15 16 in 100 mm OPENING FOR 3 8 FLEX CONDUIT 1 23 32 in 30 mm 2 1 4 in 57 mm 11 32 in 10 mm 1 1 in 28 5 mm Figure 25 Dimensions and Service Envelope of the Actuators in Tandem Application in Inches Millimeters 25 32 in 20 mm E...

Page 13: ...ue Torque Rating x Damper Area Select the total quantity of actuators required Number of Actuators Total Damper Torque required SF see note below Actuator Torque refer to specifications x NOTE When calculating the number of actuators required a safety factor SF should be included for unaccountable variables such as slight misalignments aging of the damper etc A suggested safety factor is 0 80 or 8...

Page 14: ...lications where use of the floor mount kit is not possible This kit contains a crank arm that changes the angular rotation into a linear stroke a support bearing ring to minimize side loading on the actuator s output bearing a mounting bracket and required mounting fasteners Figure 3 Crank Arm Kit ASK71 3 This kit allows a direct coupled actuator to provide an auxiliary linear drive This crank arm...

Page 15: ...ng Shaft Adapter 985 004 The self centering shaft adapter will attach to a shaft up to 1 00 inch 25 4 mm in diameter The special shaft adapter will attach to a 1 05 inch 26 6 mm diameter shaft This shaft adapter is 13 16 inch 20 mm taller than the height of the special shaft adapter EA0498R1 EA0499R1 EA0497R1 EA0500R1 Service Parts 985 003 Position indicators package of 10 ASK74 1U Special Shaft A...

Page 16: ...6 Zero Span Control Signal Adjustment ZS option EAI EN 6 7 Wiring EAI EN 7 General EAI EN 7 Transformer EAI EN 8 Three Position Floating Control 24 VAC EAI EN 8 Modulating Control 24 VAC EAI EN 8 Start up Commissioning EAI EN 9 Three Position Floating Control 24 VAC EAI EN 9 Modulating Control 24 VAC EAI EN 10 Actuator Dimensions EAI EN 11 12 Actuator Sizing for Dampers EAI EN 13 Accessories EAI E...