TYPICAL WIRING DIAGRAM
NOTE: Larger versions of the Typical Wiring Diagrams are available in the products’
operator manuals, refer to DSE Publication: 057-310 DSE8910 Operator Manual & 057-311
DSE8920 Operator Manual, both available from www.deepseaelectronics.com.
Deep Sea Electronics Ltd.
Tel:+44 (0)1723 890099
Email: [email protected]
Web: www.deepseaelectronics.com
Deep Sea Electronics Inc.
Tel: +1 (815) 316 8706
Email: [email protected]
Web: www.deepseaelectronics.com
D E E P S E A E L E C T R O N I C S
DSE8910 & DSE8920 Installation Instructions
053-248
ISSUE: 1
ACCESSING THE RUNNING CONFIGURATION EDITOR
•
The
Running Configuration Editor
is accessible without stopping the generator. All protections
remain active whilst the ‘
Running Configuration Editor
is accessed.
•
Press and hold the
Tick
button to enter the
Running Configuration Editor
.
EDITING A PARAMETER
•
Enter the
Running Configuration Editor
as described above.
•
Press the
Up
or
Down
buttons to select the section to view/change. The current selected
section highlights in green.
•
Press the
Left
or
Right
buttons to select the Subsection/Parameter to be edited. The
current selected item highlights in green.
•
To edit the parameter, press the
Tick
button to enter the edit mode. The parameter is no
longer highlighted green to indicate editing.
•
Press the
Up
or
Down
buttons to change the parameter to the required value.
•
Press the
Tick
button to save the value. The parameter highlights green to indicate that it has
been saved.
•
To exit the editor and save the changes, press and hold the
Tick
button.
SELECTING THE DSE8910 OR DSE8920 SOFTWARE APPLICATION
•
Ensure the generator is at rest and the module by pressing the
Stop/Reset Mode
button.
•
Enter the
Running Configuration Editor
as described above.
•
Press the
Up
or
Down
buttons to navigate to the
MODEL TYPE
section. The section
highlights in green when selected.
•
Press the
Right
button to select the
MODEL SELECTION
parameter. The parameter
highlights in green when selected.
•
To edit the parameter, press the
Tick
button to enter the edit mode. The parameter is no
longer highlighted green to indicate editing.
•
Press the
Up
or
Down
buttons to change between DSE8910 and DSE8920, by default
DSE8920 is selected.
•
Press the
Tick
button to change the software application, a confirmation box appears.
•
Press the
Left
or
Right
buttons to select
YES
to confirm software application change.
When prompted, remove the power supply to the module and then reapply the power supply. The
module powers up in the newly selected software application.
NOTE: If the editor is left inactive for the duration of the LCD Page Timer, it is automatically
exited to ensure security.