10.2.10 Using the fixed-speed boiler
Using the boiler according to heat input makes it possible to calibrate the
gas valve.
The heat input corresponds to the speed of the boiler in percentage of the
nominal output.
1. From the home screen, press the
and
MENU
keys simultaneously.
2. Select the parameter Controller stop function by turning the
button.
3. Press the button to confirm.
The parameter Controller stop function On appears.
4. Press the button to confirm.
304:Controller stop appears.
5. Press the button to modify the heat input value from 0 to 100 % by
turning the
button.
6. Press the button to confirm the heat input.
Important
Press the
MENU
key to return to the main display and reactivate the
control system.
For more information, see
Setting the air/gas ratio (maximum heat input), page 61
Setting the air/gas ratio (reduced heat input), page 63
10.2.11 Selecting a heating circuit
The control panel can manage up to three different heating circuits.
1. From the home screen, turn the
button to select one of the three
heating circuits available.
2. Press the button to confirm.
3. Turn the
button to temporarily modify the temperature set point on
the selected heating circuit.
4. Press the button to confirm.
The selected heating circuit is active.
Fig.86
MW-3000085-EN-02
MENU
14:13
1.5 bar
18. February 2014
Tuesday
MENU
Fig.87
MW-3000088-EN-02
MENU
Controller stop function
On
Fig.88
MW-3000089-EN-02
MENU
80%
Adjust?
304:Controller stop function
Controller stop setpoint
0%
100%
10 Settings
7702703 - v04 - 05092019
IX
91