7.5.2.
Cleaning the plate exchanger
Depending on the water quality and the operating mode, limescale
deposits may form in the plate exchanger. Periodic descaling may
therefore be necessary. As a general rule, a periodic inspection, along
with cleaning, if necessary, is sufficient. The following factors may
affect the periodicity:
4
Water hardness.
4
Composition of the limescale.
4
Number of hours' operation of the boiler.
4
Draw-off rate.
4
Domestic hot water set point temperature.
If descaling of the plate exchanger is necessary, proceed as follows:
1. Close the main water valve.
2. Drain the boiler.
WARNING
¼
To drain the boiler tanks, see chapter: "Replacing
3. Remove the air vent hose above the siphon.
4. Remove the siphon.
5. Remove the clip holding the heating flow hose in place on the left
side of the hydroblock.
6. Dismantle the heating flow hose on the left side of the hydroblock
and not on the heat exchanger side (heating circuit).
7. Unscrew the 2 hexagonal socket screws located to the right and
left of the plate exchanger.
8. Slightly turn the plate exchanger and carefully remove it from the
boiler.
9. Clean the plate exchanger with a descaling product (e.g. citric acid
with a pH of approximately 3). To do this, a specific cleaning
appliance is available as an accessory. After cleaning, rinse
thoroughly under running water.
10.Re-assemble all of the components.
T001622-C
3
4
5
6
7
7
3
2
1
8
H
2
O
2
1
+/+ H
2
O
MCA 25/28 BIC
7. Checking and maintenance
15/06/12 - 300022159-001-01
89
Summary of Contents for Innovens MCA 25/28 BIC
Page 7: ...15 06 12 300022159 001 01 5 ...
Page 122: ...9 Spare parts MCA 25 28 BIC 120 15 06 12 300022159 001 01 ...
Page 123: ......