5.4.2.
Setting the air/gas ratio (Full load)
1. Unscrew the plug of the flue gas measurement point.
2. Connect the flue gas analyser.
WARNING
Ensure that the opening around the sensor is completely
sealed when taking measurements.
3. In the main display, press key
-
. The menu
EMISSION
MEASUREMENTS
is displayed on the screen.
If an automatic vent cycle is running, it is not possible to
perform these operations.
4. Select the generator desired. The characteristics of the generator
are displayed.
5. Turn the rotary button until
PMAX
is displayed. The full load is set.
6. Measure the percentage of O
2
or CO
2
in the flue gases (Front
panel removed) .
T001581-A