8 Troubleshooting
8.1
Resolving operating errors
If the boiler malfunctions, a code is displayed on the main screen of the
control panel. This code is important for the correct and rapid diagnosis of
the type of malfunction and for any technical assistance that may be
needed.
There are 3 types of error:
Tab.43
Type of code
Code format
Error
Hxx.xx
Fault
Exx.xx
Alarm
Axx.xx
1. Make a note of the code displayed on the screen.
2. Remedy the problem described by the error code or contact the
installer.
3. Switch the boiler off and back on to check that the cause of the error
has been removed.
4. If the code is displayed again, contact the installer.
8.2
Error codes
An error code is a temporary status resulting from the detection of an
anomaly on the boiler.
When one of the codes below is displayed, contact the professional
responsible for maintenance of the boiler.
Tab.44 List of error codes
Error code
Message
Description
H00.00
TFlow Open
Flow temperature sensor is either removed or measures a temperature below
range
H00.01
TFlow Closed
Flow temperature sensor is either shorted or measures a temperature above
range
H00.06
TReturn Missing
Return temperature sensor was expected but not detected
H00.16
DHW sensor Open
Domestic Hot Water tank temperature sensor is either removed or measures a
temperature below range
H00.17
DHW sensor Closed
Domestic Hot Water tank temperature sensor is either shorted or measures a
temperature above range
H00.32
TOutside Open
Outside temperature sensor is either removed or measures a temperature
below range
H00.33
TOutside Closed
Outside temperature sensor is either shorted or measures a temperature
above range
H00.79
TSwimming Pool Open
Swimming Pool Flow temperature sensor is either removed or measures a
temperature below range
H00.80
TSwimmingPool Closed
Swimming Pool Flow temperature sensor is either shorted or measures a
temperature above range
H01.03
Flame Loss Warning
Warning off uninteded flame loss detection
H02.00
Reset In Progress
Reset In Progress
H02.02
Wait Config Number
Waiting For Configuration Number
H02.03
Conf Error
Configuration Error
H02.04
Parameter Error
Parameter Error:
H02.05
CSU CU mismatch
CSU does not match CU type
H02.09
Partial block
Partial blocking of the device recognized
H02.10
Full Block
Full blocking of the device recognized