5.6.3.
Professional settings
1. Access the installer level: Press key
-
for around 5 seconds.
2. Set the following parameters:
4
Turn the rotary button to scroll through the menus or
modify a value.
4
Press the rotary button to access the selected menu
or confirm a value modification.
¼
For a detailed explanation of menu browsing, refer to
the chapter: "Browsing in the menus", page 31.
Installer level - #PRIMARY LIMITS menu
Parameter
Adjustment range Description
Factory setting
Customer setting
BOILER MAX
20 to 90 °C
Maximum boiler temperature
75 °C
MAX.R.HEAT
(1)
0-100%
Maximum boiler output during heating 100%
MAX.DHW
(1)(2)
0-100%
Maximum boiler output in DHW
100%
MIN.VENT.
(1)
1000-5000 rpm
Minimum fan speed
See table hereafter
MAX.VENT.
(1)
1000-7000 rpm
Maximum fan speed setting in heating See table hereafter
START RPM
(1)
1000-5000 rpm
Optimum start-up speed setting
See table hereafter
MIN.PUMP SPEED
(1)
20-100%
Minimum pump speed
20 %
MAX.PUMP SPEED
(1)
20-100%
Maximum pump speed
60 %
(1) The parameter is only displayed if
INSTALLATION
parameter is set to
EXTENDED
(2) The parameter is only displayed if
P.DHW
is set to
PUMP
Type of gas used Parameter
Unit C 330-5 C 330-6 C 330-7 C 330-8 C 330-9 C 330-10
Gas H (G20)
MIN.VENT.
rpm
1400
1500
900
1000
1100
1000
MAX.VENT.
rpm
5200
5500
3500
3800
4300
4100
START RPM
rpm
2500
2500
1300
1400
1400
1400
Type of gas used Parameter
Unit C 630-5 C 630-6 C 630-7 C 630-8 C 630-9 C 630-10
Gas H (G20)
MIN.VENT.
rpm
1900
1800
1300
1200
1400
1300
MAX.VENT.
rpm
5200
5500
3500
3800
4300
4100
START RPM
rpm
2500
2500
1400
1400
1500
1600
Installer level - #SECONDARY LIMITS Menu
Parameter
Adjustment range Description
Factory setting
MAX.CIRC.A
30 to 95 °C
Maximum temperature (Circuit A)
75 °C
MAX.CIRC.B
20 to 95 °C
Maximum temperature (Circuit B)
50 °C
MAX.CIRC.C
20 to 95 °C
Maximum temperature (Circuit C)
50 °C
(1) The parameter is only displayed if
INSTALLATION
is set to
EXTENDED
(2) The parameter can be set to the heating curve by pressing key
f
.
1
1
2
2
r
c
STD
(
'
t
v
0
2
4
6
8
10
12
14
16
18
22
24
20
p
b
AUTO
x c
r
j
M
g
m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
5. Commissioning
Diematic iSystem For C 330 / C 630 ECO
53
31082018 - 7600691-001-06