6 Connecting diagrams and configuration
6.1
Factory settings for circuits
In the factory, the different circuits are configured as indicated in the table.
You can modify this configuration and adapt it to the needs of your
installation. Three installation types are described here to provide a guide.
Tab.4
Circuit
Circuit type
Specifications
CIRCA
Direct heating circuit
Gradient: 1.5
Maximum temperature: 90 °C
CIRCB
CIRCC (optional)
AUX (optional)
Circuit with mixing valve
Gradient: 0.7
Maximum temperature: 50 °C
DHW
Domestic hot water circuit
Set point temperature: 55 °C
6.2
Addition of 2 heating ci 1 DHW c 1 swimming pool circuit controlled by VM
Diematic Evolution
Tab.5
Packages used in this configuration
AD199
Flow sensor after valve
AD249
Three-way valve PCB and sensor
AD212 (x3)
Domestic hot water sensor and TAS
AD309
S-Bus 12 m cable with terminals
AD311
SmartTC° programmable and connected room thermostat
AD250
Sensor for buffer tank or cascade flow
6 Connecting diagrams and configuration
16
7703592 - v02 - 14062018