During cleaning, avoid possible damage due to aggressive solvents, water jets or abrasive materials. Clean
with a damp cloth.
Once a year all electrical connections must be checked. The charging station must be opened and checked
internally only by qualified electrician.
5.1. Differential protection test
To guarantee an adequate service it is recommended to supply the station with a dedicated line as well as
each socket equipped inside is individually protected with magnetothermal differential switches. The
differential devices must be checked periodically according to the regulations in force; in the absence of
national regulations, manufacturers recommend checking each month.
Acting on the test button the device must intervene immediately. Otherwise contact your trusted technician
because the safety of the system is no longer guaranteed and people are not protected against direct and
indirect contacts.
The presence of such a protection device does not exempt from observing all the precautions connected to
the use of electric current.
5.2. Assistance
In case of need for assistance, contact the DazeTechnology Srl Service Department or (after the expiry of
the warranty period) the manufacturer of the relevant part of the machine not built by Daze Technology Srl.
Warning: Access to the inside of the electrical box is allowed only to qualified and authorized service
personnel.