Interval time to send an uplink message regardless of any conditions
constant_A | Default = calibrated value by factory
This value will affect the measurement accuracy.
DO NOT change this value!
Those configuration parameters can be changed by downlink or offline tools. For more other configuration parameters,
please refer to the next section.
Sensor configuration can be configured in 02 methods:
Method 1: Configuring via Downlink message. Please find the instructions in
, but please take note of
the
FW version of the Document.
.
Some parameters are read-only, and some are read and writeable.
To read the parameters, use the off-line cable as above instruction.
Via uplink message, users can read only one parameter, which is the CURRENT_CONFIGURATION.
Below tables are the lists of the parameters of the device.
Read-only Parameter Table
Modbus
Register
(Decimal)
Modbus
Register
(Hex)
Function
Code (Read)
No. of
Registers
Description
Range
Format
Property
Comment
2
2
3
4
FW_VERSION
string
Read
6
6
3
2
HW_VERSION
string
Read
8
8
3
2
DEVICE_ID
hex
Read
Product ID
10
A
3
4
DEVICE_PAC
hex
Read
Product PAC
14
E
3
1
SENSOR_TYPE
1-255
uint16
Read
Sensor or
Input Type
Read/Write Parameter Table
Modbus
Register
(Decimal)
Modbus
Register
(Hex)
Function
Code
(Read)
Function
Code
(Write)
No. of
Registers
Description
Range
Default
Format
Property
Comment
270
10E
3
16
4
CURRENT_CONFIGURATION
hex
Read/Write
Check the
section:
5.
Payload
for
downlink
message
for more
information
274
112
3
16
1
SERVER_CONFIG
0
uint16
Read/Write
0: Send to
Sigfox
Network
1: Send to
Dongle
276
114
3
16
1
RADIO_CONFIG
1-4
4
uint16
Read/Write
RC zones
selection
1, 2 , 3, 4
is RC1,
RC2,
RC3s, RC4
3.2 Sensor Configuration
3.2.1 How to configure the Sigfox-Ready V1A Sing-axis Vibration Sensor?
3.2.2 What parameters of the device are configured?