background image

 

 

 

Technical Support:

Main:

201-934-5111
201-934-9944

[email protected]
Website: dataprobe.com

Download the complete iPIO-8 Installation and Operation manual as well as the latest firmware and any 
utilities at: 

http://dataprobe.com/ipio8-web-relay-control.html?Support

 

 

Overview 

 
The iPIO-8 is a network attached, IP addressed digital input and output device.  The iPIO-8 can be 
controlled and monitored with a standard web browser.  Multiple iPIO-8 devices can communicate 
amongst themselves to transport I/O information across the network.  Each iPIO-8 has eight controllable 
form C relays, and eight digital inputs. 
 

Hardware Installation 

Inputs  

Connect the inputs to the iPIO-8 using the removable 
screw terminals.  Connect only dry contact closures; relay 
or switch contacts.  Connect one leg to the G terminal and 
the other to the + terminal. 
 
For information on connecting wet contacts, consult the 
complete manual before making any connections. 
 

Relays 

Connect to the iPIO-8 relays using the removable screw 
terminals.  Relays are Form C.  Connect to the Common 
(C), Normally Closed (NC) and Normally Open (NO) as 
marked.  When the iPIO-8 relay is in the Open Condition, 
the Common is connected to the Normally Open.  In the 
Closed state, the Common and Normally Closed are 
connected. 
 
Relay Specifications 
 

Rating (resistive)   

0.5 A 120 VAC or 1 A 24 VDC 

Maximum Carrying Current 

2 A 

Maximum Switching Power 

60 AV, 24 W 

Maximum Switching Voltage 

120 VAC/60 VDC 

Maximum Switching Current 

1A 

Life Expectancy 

5 Million Operations Mechanical.  
100K Operations at rated load 

 
 

 

 

 

 

 

 

iPIO-8 

Ethernet I/O Monitor and Control 

Quick Start Guide 

Reviews: