SG4-Extended SERIES

 

 

Safety light curtains with infrared beams

 

 
 
 

QUICK GUIDE 

 

SAFETY INFORMATION 

 

The following points must be observed for a correct and safe use 

of the safety light curtains of the SG4-Extended series. 

 

 The stopping system of the machine must be electrically controlled. 

 

 This control system must be able to stop the dangerous movement of the machine within the total machine stopping 

time T as per paragraph 1.3.3 of the manual included in the supplied CD and during all working cycle phases. 

 

 Mounting and connection of the safety light curtain must be carried out only by qualified personnel, according to the 

indications included in the special sections (refer to sections 2; 3; 4; 5 of user manual) and in respect to the applicable 
Standards. 

 

 The safety light curtain must be securely installed so that access to the dangerous zone is not possible without 

interrupting the beams (see chapters 2, 3 of user manual). 

 

 The personnel operating in the dangerous area must be well-trained and must have adequate knowledge of all the 

operating procedures of the safety light curtain. 

 

 The TEST, RESET/RESTART and OVERRIDE buttons must be located outside the protected area as the operator must 

check the protected area during all Test, Restart and Override operations. 

 

 Please carefully read the instructions for the correct functioning before powering the light curtain. 

 
Precautions to be observed for the choice and installation of the device 
 

 

Make sure that the protection level assured by the SG4-E device is compatible with the real 

danger level of the machine to be controlled, according to EN 954-1 and EN 13849-1. 

 

 The outputs (OSSD) of the ESPE must be used as machine stopping devices and not as command devices. The 

machine must have its own START command. 

 

 The dimension of the smallest object to be detected must be larger than the resolution level of the device. 

 

 The ESPE must be installed in a room complying with the technical characteristics indicated in section 11 “Technical 

data” of the manual included in the CD supplied. 

 

 Do not place the device near intense and/or flashing light sources and, in particular, close to receiving unit front surface. 

 

 The presence of intense electromagnetic disturbances could jeopardize device operation. This condition has to carefully 

evaluated with the support of the DATALOGIC Technical service. 

 

 

 The operating distance of the device can be reduced in presence of smog, fog or airborne dust. 

 

 A sudden change in environment temperature, with very low minimum peaks, can generate a small condensation layer 

on the lenses and so jeopardize functioning. 

 

 Reflecting surfaces near the safety light curtain light beam (above, under or lateral) can cause passive reflections that 

can jeopardize functioning. 

 

 The safety device must be installed at a distance which is major or equal to the minimum safety distance S to ensure 

that the operator cannot reach the dangerous area until the moving dangerous object has been blocked by the ESPE. 

 

 

The failure to respect the safety distance reduces or cancels ESPE protection function. 

For more detailed information about calculation of safety distance, please refer to the 

complete manual contained in the supplied CD. 

 

Summary of Contents for SG4-Extended SERIES

Page 1: ...he SG4 E device is compatible with the real danger level of the machine to be controlled according to EN 954 1 and EN 13849 1 The outputs OSSD of the ESPE must be used as machine stopping devices and not as command devices The machine must have its own START command The dimension of the smallest object to be detected must be larger than the resolution level of the device The ESPE must be installed...

Page 2: ...11 OVERRIDE STATUS grey pink 12 EARTH red blue M12 5 pole 1 24V brown 2 MUTING2 white 3 0V blue 4 MUTING1 black 5 N C grey SG4 E TX M12 5 pole 1 24V brown 2 TEST white 3 0V blue 4 EARTH black 5 N C SG4 E RX Blanking Operation M12 12 pole 1 24V brown 2 0V blue 3 RESET RESTART ALIGN white 4 TEACH IN green 5 OSSD2 pink 6 EDM yellow 7 N C black 8 OSSD1 grey 9 TOLERANCE red 10 LAMP violet 11 N C grey p...

Page 3: ...t the emitter until the yellow SYNC 1 LED is OFF This condition shows the effective alignment of the first synchronisation beam B Rotate the emitter pivoting on the lower optics axis until the yellow SYNC 2 LED is OFF C Delimit the area in which alignment is good and steady through some micro adjustments for the first and then for the second unit so to have the maximum alignment LEVEL and then pla...

Page 4: ...ration Mode A Test Pattern is shown on led interface carefully check that ALL led are lit in sequence from 1 to 8 then current configuration is shown B Choose function to set by SELECT button selected led blinks C Configure selected function with ENABLE button switch led on off Repeat B C steps until desired configuration is visualized E Keep CONFIRM button pressed to authorize the new configurati...

Page 5: ...ting default in bold Led Status Code 1 Code 2 Coding 2 No Code Long Range Selection 3 Short DIAGNOSTICS FUNCTION The operator can visualize the operating condition of the light curtains thanks to the 8 led positioned on both the RX and TX unit SG The figure below shows all signalling LEDs modes OFF ON BLINKING INDIFFERENT Can be both On or Off depending on actual working mode RX UNIT ESPE Working ...

Page 6: ...unication failure Check cascade connection and correct mounting of terminator cap Activate RESET line FAILURE LOCKOUT BCM Configuration failure Re operate Basic Configuration If error persists contact Datalogic Technical Support FAILURE LOCKOUT ACM Configuration failure Re operate Advanced Configuration If error persists contact Technical Support Make sure the most recent version of the GUI availa...

Page 7: ...EMISSION TEST Short Range Emission EMISSION TEST Long Range Emission EMISSION TEST No code EMISSION TEST Code 1 EMISSION TEST Code 2 FAILURE LOCKOUT Failure on micro processor s Activate RESET line If error persists contact Datalogic Technical Support FAILURE LOCKOUT Failure on optics Activate RESET line If error persists contact Datalogic Technical Support FAILURE LOCKOUT BCM Configuration failur...

Page 8: ... from the improper application of DATALOGIC products DATALOGIC AUTOMATION srl Via Lavino 265 40050 Monte S Pietro Bologna Italy Tel 39 051 6765611 Fax 39 051 6759324 www datalogic com DATALOGIC cares for the environment 100 recycled paper DATALOGIC reserves the right to make modifications and improvements without prior notification 2011 2013 Datalogic Automation ALL RIGHTS RESERVED Protected to th...