S100W
Instruction Manual
CONTROLS
OUTPUT LED – Yellow
The yellow LED indicates the output status.
Please refer to “Settings” for the correct use procedures.
INSTALLATION
The sensor can be positioned by means
of the two housing’s threaded holes (M3)
using two screws (M3x12 or longer or
M2.5 passing screw, 0.4 Nm maximum
tightening torque) with washers or by
mean of the two rear holes using two
M3 passing screw, 0.4Nm maximum
tightening torque.
CONNECTIONS
DIMENSIONS
TECHNICAL DATA
Power Supply
10 ... 30 VDC (Class 2 UL508) (reverse polarity protected)
Ripple
10% max.
Current consumption (output current
excluded)
35 mA max.
Output / Alarm output
PNP or Push-Pull (short-circuit protection)
Output current
100 mA max.
Output saturation voltage
≤ 2 V
Input
REMOTE (S100W-..-PK)/Pin 2 can be configured as a REMOTE input through IO-Link (S100-..-OZ).
The input cannot be kept disconnected.
Response time
25 μs
Switching frequency
20 kHz
Emission type
blue (465 nm) / green (520 nm) / red (630 nm)
with automatic selection
Exempt Risk Group (RG0) for IEC 62471
Spot dimension
6.5 mm x 1.5 mm
Operating distance (typical values)
12.5 mm
Depth of field
± 2 mm
LIGHT/DARK selection
Automatic
Indicators
Output LED (yellow)
Operating temperature
-25 ... 55 °C
Storage temperature
-40 ... 70 °C
Dielectric strength
1500 VAC 1 min. between electronics and housing
Insulating resistance
>20 MΩ 500 Vdc between electronics and housing
Ambient light rejection
according to EN 60947-5-2
Vibrations
0.5 mm amplitude, 10 … 55 Hz frequency, for each axis (EN60068-2-6)
Shock resistance
11 ms (30 G) 6 shocks for each axis (EN60068-2-27)
Housing material
Body in ABS; indicators cover in PMMA
Lens material
Frontal window in PMMA; lens in PC
Mechanical protection
IP67
Connections
M8 4-pole connector
Weight
12 g. max
SETTINGS
S100W – REMOTE input
The REMOTE signal carries out acquisition functions without using the IO-
Link.
Configure the N.C. output as a REMOTE input through the IO-Link.
Datalogic S.r.l.
Via S. Vitalino 13 - 40012 Calderara di Reno - Italy
Tel: +39 051 3147011 - Fax: +39 051 3147205 - www.datalogic.com
Helpful links at www.datalogic.com:
Contact Us, Terms and Conditions, Support.
The warranty period for this product is 36 months. See General Terms and Conditions of
Sales for further details.
For information about the disposal of Waste Electrical and Electronic Equipment
(WEEE), please refer to the website at
.
© 2020 Datalogic S.p.A. and/or its affiliates - ALL RIGHTS RESERVED. - Without limiting the rights under copyright,
no part of this documentation may be reproduced, stored in or introduced into a retrieval system, or transmitted
in any form or by any means, or for any purpose, without the express written permission of Datalogic S.p.A. and/
or its affiliates. Datalogic and the Datalogic logo are registered trademarks of Datalogic S.p.A. in many countries,
including the U.S.A. and the E.U. All other trademarks and brands are property of their respective owners. Datalogic
reserves the right to make modifications and improvements without prior notification.
821006951 Rev. B
Dimensions in mm
The operating distance is measured from
the front surface of the sensor optics.
Mark detection on a reflective surface is
improved adjusting the beam direction to
5° … 20° from surface axis.
S100W
S100W IO-LINK
®
FINE ACQUISITION
Mark detection
The LIGHT/DARK mode is automatically selected
by the sensor.
Place the mark in front of the sensor spot and send
the IO-Link command.
The sensor functions alternating red, green and
blue emissions.
Do not move the mark during this phase.
Background detection
Place the background in front of the sensor spot
and send the IO-Link command.
The sensor functions alternating red, green and
blue emissions.
Do not move the background during this phase.
DYNAMIC ACQUISITION
Use dynamic acquisition to acquire moving marks.
The sensor detects the contrast between the mark
and the moving background, and automatically sets
the threshold value. The LIGHT/DARK mode must
be set in advance.
ACQ.
If the LED blinks slowly the acquisition failed due to insufficient contrast.
Press SET and the sensor returns to the previous setting. Repeat the
procedure from the beginning. Check the acquisition status on the process
data.
The sensors are NOT safety devices, and so MUST NOT be used in the
safety control of the machines where installed.