LOW VOLTAGE ELECTRICAL CONNECTIONS

8

   PWR-240B

DC OK Monitoring

The DC voltage terminal block provides two wiring terminals (13-14), which monitor the

status of the switching power supply (DC OK feature). When the power supply module

runs correctly, lines 13 and 14 form a normally closed contact.  If the power module

experiences problems (i.e. output overload causing output voltage to be reduced by less

than 90% of nominal) these lines open. Lines 13 and 14 are decoupled from the power

output lines and can be connected to a free digital input to signal this alarm condition.

DC Direct Output

The 24 volt DC Output terminals are direct. Connect the output devices according to

your application requirements.

LASER BARCODE SCANNERS

Supply Capacity When Wiring Directly to AS-I Compatible Scanners

For direct wiring, power distribution is performed simultaneously for all the scanners.

However all the scanner motors start up slowly so that there is no significant peak cur

-

rent draw. See the specific scanner manual for consumption data.

The maximum number of same type scanners to be supplied for direct wiring the PWR-

240B is shown in the table below and depends on the wiring topology:

The following products are also AS-I compatible: DS5100, DM3610, SC5000. In case of

networks using a mix of products, you must calculate the total power consumption so as

not to exceed the limits for the specific topology used. See the specific product refer

-

ence manual in the Technical Features chapter for consumption data.

The power supply unit is connected directly to the scanners via AS-I cabling.

SCANNER TYPE

MAXIMUM NUMBER OF SCANNERS BY 

TOPOLOGY

DOUBLE BRANCH

SINGLE BRANCH

DS8110

11 (balanced 6+5)

9

DX8210

11 (balanced 6+5)

9

AS-I Single Branch

200 W max

AS-I Double Branch

240 W max total (200 W max for a single branch)

Summary of Contents for PWR-240B

Page 1: ...PWR 240B INSTALLATION MANUAL Reading Station Power Supply...

Page 2: ...ion and shall ensure that all notices appear on any reproductions of the documentation Electronic versions of this document may be downloaded from the Datalogic website www data logic com If you visit...

Page 3: ...TALLATION 5 Cabinet Mounting 5 CHAPTER 4 LOW VOLTAGE ELECTRICAL CONNECTIONS 6 DC Low Voltage Cable Insertion 6 Cable Entry Plate 6 AS I Cable Insertion 7 DC Voltage Terminal Block 7 DC OK Monitoring 8...

Page 4: ...to download Data Sheets Manu als Software Utilities and Drawings Hover over the Support Service menu for access to Services and Technical Support Reseller Technical Support An excellent source for te...

Page 5: ...conformity is a living document The EU declaration of conformity is available for competent authorities and customers through Datalogic commercial reference contacts Since April 20th 2016 the main Eur...

Page 6: ...Key Lock 6 Cooling Fan 2 Product Data Label 7 AC Line Input Terminal Block 3 AC Input Cable Compression Connector 8 Thermal magnetic Circuit Breaker 4 Cable Entry Plate with Grommets 9 DC OK Terminal...

Page 7: ...direct connection block The direct connection block is protected by the internal power supply features Two output power supply status monitoring signals DC OK are provided to connect to an optional di...

Page 8: ...s a reduction in voltage below 13V This causes the power supply to enter HICCUP operation where power is supplied for 2 seconds and then shuts off for 18 seconds This procedure is repeated until the s...

Page 9: ...lication Barcode Scanners Correctly connect the AS I cabling to the PWR using the AS I cable wiring instruc tions for backbone and branch wiring See Laser Barcode Scanners on page 8 and your scanner m...

Page 10: ...2 3 the AC input cable must have a maxi mum diameter of 14mm and the conduit a max diameter of 16mm 5 With AC line voltage OFF wire the AC Line to the AC Line Input Terminal Block see AC Line Input Vo...

Page 11: ...unt the bracket to the cabinet 2 Mount the cabinet to the frame Figure 5 Mounting Brackets Figure 6 PWR 240B cabinet max height Please note that the cabinet door can be unlocked and opened by using th...

Page 12: ...he Cable Entry Plate and select all the necessary grommets for your application 3 Insert the correct size sealing grommets and positions relative to these cables Unused positions must mount the closed...

Page 13: ...sitioning Strip the individual wires for insertion into the Terminal Block Figure 7 AS I Cable Prep Pass the AS I cable through the AS I cable sealing grommet and make sure there is enough length to e...

Page 14: ...iring power distribution is performed simultaneously for all the scanners However all the scanner motors start up slowly so that there is no significant peak cur rent draw See the specific scanner man...

Page 15: ...240B Directly to Scanners Refer to the specific scanner manual for I O interface wiring connections AS I Wiring Topologies Figure 11 Single Branch Topology 24 Vdc to scanners using AS I cabling DC OK...

Page 16: ...Y INDUSTRIAL ETHERNET SWITCH An accessory 24 Vdc Industrial Ethernet Switch can be installed and powered from inside the PWR 240B power supply Figure 13 24 Volt Industrial Ethernet Switch device nodes...

Page 17: ...UAL 11 Fix the Industrial Ethernet Switch to the DIN rain using the clips provided inside the PWR and connect the power cables as shown in the figure below Figure 14 Industrial Ethernet Switch Mounted...

Page 18: ...sconnector and Distributor cabinet which provides this protection For primary wiring use a 3 conductor cable between 2 5 mm2 4 mm2 13 AWG 11 AWG for every conductor Choose the overall cable diameter a...

Page 19: ...PWR 240B AC Line Terminal Block with Protection Covers The terminal block marked with the ground symbol is a special block which allows direct connection of the Protection Earth with the enclosure of...

Page 20: ...er Block The DC Power Block connects to the AC input line and Its AC cord must be adapted to connect to the PWR AC input terminal block Cut the power block AC cord to about 30 cm 12 in from the female...

Page 21: ...ALLATION MANUAL 15 Figure 18 Fixing the 12 Vdc Power Block inside the PWR 240B Pass the 12 Vdc output cable through the correct size grommet in the cable entry panel holder pass two tie wraps under ne...

Page 22: ...Current Consumption Max 6 A Icp 10kA output at full load Output Voltage 24 Vdc Nominal Output Current 10 A Max Continuous Overcurrent 12 A up to 45 C ambient temp ENVIRONMENTAL FEATURES Operating Tem...

Page 23: ...INSTALLATION MANUAL 17 APPENDIX A ELECTRICAL DIAGRAMS PWR 240B ELECTRICAL DIAGRAM The PWR 240B components are electrically connected as displayed in the following dia gram...

Page 24: ...m AK1 DIN BAR LINE PE LINE N LINE L 4 0 mm 4 0 mm F0 N L 6 A DIN BAR 2 5 mm 2 5 mm N01 L01 N01 L01 L01 N01 2 5 mm 2 5 mm 2 5 mm T10 1 0 mm 1 0 mm 4 0 mm 4 0 mm 0 2 mm 0 2 mm T10 ALARM 13 T10 ALARM 14...

Page 25: ......

Page 26: ...yright no part of this documentation may be repro duced stored in or introduced into a retrieval system or transmitted in any form or by any means or for any purpose without the express written permis...

Reviews: