CBX ELECTRICAL CONNECTIONS
66
MATRIX 320
ID-NET INTERFACE
CBX100/500
Description
Shield
Network Cable Shield
ID+
ID-NET Network Data +
ID-
ID-NET Network Data -
REF
Network Reference
ID-NET Cables
The following instructions are referred to Figure 48, Figure 49 and Figure 50.
•
The general cable type specifications are: CAT5 twisted pair + additional CAT5
twisted pair, shielded cable AWG 24 (or AWG 22) stranded flexible.
We recommend using DeviceNet cables (drop or trunk type) to the following refer-
ence standards:
AN50325 – IEC 62026
UL STYLE 2502 80°C 30V
•
Cable Shield MUST be connected to earth ground ONLY at the Master.
•
NEVER use ID-NET cable shield as common reference.
•
The ID-NET max cable length depends on the baudrate used (see the Baudrate
Table below).
•
For Common Power Connections use only 2 wires (ID+ and ID-).
- DC Voltage Power cable (Vdc – GND) should be handled as a signal cable (i.e. do
not put it together with AC cable):
- Wire dimensioning must be checked in order to avoid voltage drops greater than
0.8 Volts.
- Cable should lie down as near as possible to the ID-NET cable (avoiding wide
loops between them).
•
Reader's chassis may be connected to earth.
•
Network inside the same building.
Baudrate Table
Baudrate
125 kbps
250 kbps
500 kbps
1 Mbps
Cable Length
1200 m
900 m
700 m
*
* Application dependent, contact your Datalogic representative for details.
NOTE
The default ID-NET baudrate is 500 kbps. Lower ID-NET baudrates allow
longer cable lengths.
Summary of Contents for Matrix 320
Page 1: ...Matrix 320 PRODUCT REFERENCE GUIDE Image Based Industrial Reader...
Page 88: ...CBX ELECTRICAL CONNECTIONS 74 MATRIX 320 Figure 54 NPN External Trigger Using Matrix 320 Power...
Page 133: ...Reader 2 Reader 3 PASS THROUGH CONFIGURATIONS PRODUCT REFERENCE GUIDE 119...
Page 141: ...INTERNAL NETWORK CONFIGURATIONS PRODUCT REFERENCE GUIDE 127...
Page 143: ...INTERNAL NETWORK CONFIGURATIONS PRODUCT REFERENCE GUIDE 129 Open the cloned application job...