background image

DPR-350 User Manual Ver_01                                                                Firmware V-1.0

 

 

 

 

DPR-350 is a state of the art network analyzer and 
protection relay in 96x96 standard panel dimensions. 
Thanks to its low depth, it provides space economy.  

The DPR-350 features dual current measurement 
circuits. It is both a precise analyzer and a protection 
relay. Protection curves can be selected among IEC, 
ANSI, UK and US standards. Multiple protection curves 
can be activated simultaneously. 

Multiple measurements can be viewed on the 128x64 
pixel graphic display of the device. 

The unit records every electrical parameter to its built-in 
1MB (16MB optional) memory at the desired sampling 
rate. The records can be read via Modbus. 

Through its RS-485 port, the unit can connect to various 
Scada systems and can be remotely monitored. 
Parameter configuration is done via USB port. 

The unit offers 4 digital inputs, 2 relay outputs, and 3 
analog outputs as standard. Analog outputs can be used 
to receive desired measurements in the form of 4-20mA 
signals, or to drive a visual fault mechanism. 

 

• 

IEC Standard / Very / Extreme Inverse 

• 

UK Long Term Inverse,  

• 

IEEE Medium / Very / Extreme Inverse 

• 

US Normal Inverse, Short Time Inverse 

 

 

• 

USB 2.0 PC connection 

• 

RS-485 (isolated) 2400-115200 baud 

• 

Modbus RTU 

• 

IEC60870-5-103 communication protocol 

 

 

• 

35x event records with time stamp. 

• 

15.000 periodic records with time stamp. 

• 

Adjustable sampling rate.  

• 

1MB total record memory. 

 

 

• 

Phase voltages: V1-V2-V3-U12-U23-U31 

• 

Phase currents: I1-I2-I3-Ineutral 

• 

Active power: P1-P2-P3-

∑P 

• 

Reactive power: Q1-Q2-Q3-

∑Q 

• 

Apparent power: S1-S2-S3-

∑S 

• 

Power factor: cos1-cos2-cos3-

∑cos 

• 

Frequency: F 

• 

Negative sequence currents and voltages 

• 

Zero sequence currents and voltages 

• 

T32Q value

 

DPR 350 

NETWORK ANALYZER & 
PROTECTION RELAY

 

 

 

• 128x64 pixels graphic displays 
• % 0.5 accuracy OG analyzer features 
• 4 quadrant energy counters 
• Multiple protection curves 
• 1MB records memory 
• Self-test, internal failure monitoring 
• Cold reclosure 
• Configurable optically isolated digital inputs 
• Configurable relay outputs 
• Configurable analog outputs 
• 2 independent configuration sets 
• English menus 
• Setup parameters on the device 
• 3-level password protection 
• Connection via USB or RS-485 
• Free PC configuration software 
• Manual open/close from front panel and  
Scada 
• Software update via USB 
• Wide supply voltage range: 19-150V

DC

 

• IP65 protection with optional gasket 
• Low panel depth 

 

• 

EN60255 Electrical Relays 

• 

EN61010 Safety Requirements 

• 

EN61326 Electromagnetic Compatibility 

• 

EN60068 Environmental Conditions 

• 

EN60529 Protection Levels 

 

ANSI CODE DESCRIPTION 

50,51 

Overcurrent 

46 

Negative Sequence Overcurrent 

67 

Directional Overcurrent 

50BF 

Breaker Failure 

79 

Reclosure 

 

            

           

 

DESCRIPTION 

PROTECTION CURVES 

COMMUNICATIONS 

RECORD MEMORY 

ANALYZER MEASUREMENTS 

FEATURES 

STANDARDS 

PROTECTION FUNCTIONS 

Summary of Contents for DPR-350 Series

Page 1: ...nt records with time stamp 15 000 periodic records with time stamp Adjustable sampling rate 1MB total record memory Phase voltages V1 V2 V3 U12 U23 U31 Phase currents I1 I2 I3 Ineutral Active power P1...

Page 2: ...echnical queries please contact Datakom at the e mail address below technical support datakom com tr If additional information to this manual is required please contact the manufacturer directly at th...

Page 3: ...ction or material damage ATTENTION Useful hints for the understanding of device operation The DPR 350 family units are available in various options and peripheral features Please use below information...

Page 4: ...DPR 350 User Manual Ver_01 Firmware V 1 0 SPARE PARTS Screw type bracket Stock Code J10P01 per unit Self Retaining type bracket Stock Code K16P01 per unit Sealing Gasket Stock Code J63P01...

Page 5: ...f 6A Disconnect all power before working on the equipment When the unit is connected to the network do not touch the terminals Short circuit terminals of unused current transformers Any electrical par...

Page 6: ...DELTA 2 CTs L1 L2 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 4 9 1 PHASE 2 WIRE 5 CONNECTION DIAGRAM 6 TECHNICAL SPECIFICATIONS 7 TERMINAL DESCRIPTIONS 8 DESCRIPTION OF CONTROLS 8 1 FRONT PANEL FUNCTIONALIT...

Page 7: ...11 DATE TIME SETTINGS 20 12 CHANGING THE PASSWORD 20 13 RETURN TO FACTORY PRESET 20 14 LOCATION SETTINGS 20 15 OVERCURRENT PROTECTION ANSI 50 51 20 16 NEGATIVE SEQUENCE OVERCURRENT PROTECTION ANSI 46...

Page 8: ...ice Incorrect connections Incorrect power supply voltage Voltage at measuring terminals beyond specified range Voltage applied to digital inputs over specified range Current at measuring terminals bey...

Page 9: ...l mounted rear retaining plastic brackets Weight 200g 0 44 lb Panel Cutout Required Panel Depth 2 MOUNTING 2 1 DIMENSIONS 2 2 MECHANICAL INSTALLATION The unit is designed for panel mounting The user s...

Page 10: ...nd connectors from the unit then pass the unit through the mounting opening Place and tighten mounting brackets Two different types of brackets are provided Screw type bracket Self retaining type brac...

Page 11: ...1 0 mm diameter and greater 5 Protected from the amount of dust that would interfere with normal operation 6 Dust tight 2nd Digit 0 Not protected 1 Protected against vertically falling water drops 2...

Page 12: ...e cable section at least 0 75mm2 AWG18 Follow national rules for electrical installation Current transformers must have 1A or 5A output For current transformer inputs use at least 1 5mm2 section AWG15...

Page 13: ...ing Rate 8192 Hz Input Voltage Range 0 300 VAC phase neutral Measurement Range 7 330VAC Ph N 14 to 520VAC Ph Ph Input Impedance 4 5M ohm Display Resolution 0 1VAC Accuracy 0 5 1 digit 230VAC Ph N 2VAC...

Page 14: ...neous power and power factor readings although the amp readings are correct It is advised CT rating to be selected following this table for the best measurement accuracy SELECTING THE CT ACCURACY CLAS...

Page 15: ...0 100 1 00 Phase L3 100 0 0 0 100 1 00 Total 300 0 0 0 300 1 00 EFFECT OF POLARITY REVERSAL The utility mains is still loaded with 100 kW on each phase The load power factor PF on Phase L2 will show 1...

Page 16: ...50 0 86 6 100 0 50 Phase L3 50 0 86 6 100 0 50 Total 0 0 0 0 300 0 0 Number of Inputs 4 inputs all configurable Input Type Optically isolated digital input Function Selection From list Contact Type No...

Page 17: ...485 line in order to provide data transfer to automation or building management systems The RS 485 port provides an effective solution for distant PC connection to enable programming and monitoring vi...

Page 18: ...igned to provide PC connection with the controller Programming and monitoring can be done via RainbowPlus program The RainbowPlus program is available for free on www datakom com tr The connector type...

Page 19: ...Ver_01 Firmware V 1 0 Topologies are selected from program parameters Mains grid topologies are shown in the picture below 4 TOPOLOGIES 4 1 TOPOLOGY SELECTION Configuration Screen Topology Selection E...

Page 20: ...DPR 350 User Manual Ver_01 Firmware V 1 0 4 2 3 PHASE 4 WIRE STAR 4 3 3 PHASE 3 WIRE DELTA...

Page 21: ...DPR 350 User Manual Ver_01 Firmware V 1 0 4 4 3 PHASE 4 WIRE DELTA 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2...

Page 22: ...DPR 350 User Manual Ver_01 Firmware V 1 0 4 6 3 PHASE 3 WIRE DELTA 2 CT L1 L3 4 7 2 PHASE 3 WIRE DELTA 2 CTs L1 L2...

Page 23: ...DPR 350 User Manual Ver_01 Firmware V 1 0 4 8 1 PHASE 2 WIRE...

Page 24: ...DPR 350 User Manual Ver_01 Firmware V 1 0 5 CONNECTION DIAGRAM...

Page 25: ...000 MW Relay outputs 5A 250VAC 30VDC Digital Inputs Active level 19 140V DC or AC Min pulse 100ms Isolation 1000V AC 1 minute USB Port USB Device full speed 12Mbit Serial Port Signal Type RS 485 Commu...

Page 26: ...ations port Connect the A B terminals of the RS 485 datalink to these terminals RS 485 B PROTECTION GROUND Grounding terminal Connect the ground terminal of the RS 485 cable to this terminal Terminal...

Page 27: ...urrent screen is assigned as main opening screen Move to next screen within the group Hold pressed for 3 seconds Manual open close screen is displayed Hold pressed together for 3 seconds Enter program...

Page 28: ...urrent Frequency Hz Total active power Total reactive power Total apparent power Total power factor Average Ph N voltage Average Ph Ph voltage Average current L1 active power kW L2 active power kW L3...

Page 29: ...ve Power kVar Q2 Phase 2 Reactive Power kVar Q3 Phase 3 Reactive Power kVar Q Total Reactive Power kVar S1 Phase 1 Apparent Power kVA S2 Phase 2 Apparent Power kVA S3 Phase 3 Apparent Power kVA S Tota...

Page 30: ...een Parameter groups are listed below Mimic Diagram Screens showing protection status Measurement Screens Voltage current kW kVA kVAr pf active and reactive energy counters Demand Screens Demand curre...

Page 31: ...tection ANSI 50 51 Negative Sequence Overcurrent Protection ANSI 46 Directional Overcurrent Protection ANSI 67 Breaker Failure ANSI 50BF Circuit Connection Supervision ANSI 74 Reclosure ANSI 79 Motori...

Page 32: ...ent TD for IEEE TMS for IEC Constant for the given curve Constant for the given curve L Constant for IEEE 0 for IEC C Constant additional delay CURVE STANDARD L Constant Time DT Standard Inverse IEC 0...

Page 33: ...gle directional protection or level 1 I protection may be programmed for forward directional protection while level 2 I can be configured for reverse directional protection The controller continuously...

Page 34: ...eaker If breaker contact information is assigned to digital inputs abnormal situations will be displayed on the device s protection screen MIMIC DIAGRAM with the following symbols SYMBOL DESCRIPTION B...

Page 35: ...ulse magnetization currents of transformers Starting currents of asynchronous motors Collective activation of air conditioning of heating loads Protections should normally be configured so as not to t...

Page 36: ...se 1 phase 2 voltage and total active power are displayed If digital inputs have been configured to breaker open and closed contact this screen displays the related error symbols For detailed informat...

Page 37: ...s systems Astronomic Timer Relay Screen Astronomic timer relay can be configured from Location Settings in programming The unit takes date and time information from its internal Real Time Clock Geogra...

Page 38: ...s are shown as 2 columns with small characters thus the screen capacity is 4 values for large characters and 16 values for small characters Small and large characters can be used on the same screen if...

Page 39: ...nters which count signal pulses for digital inputs This allows for counting and reading external events with communication channels Counters Total import kWh 1 Total export kWh 1 Total inductive kVArh...

Page 40: ...e device is active it compares actual values to recorded values If the actual value fulfills the condition greater than max value or lower than min value it is recorded as the new value Min max values...

Page 41: ...apparent power kVA total power factor total harmonic distortion V1 V2 V3 U12 U23 U31 I1 I2 I3 Events that trigger records can be selected as shown below Alarm events Recorded if an alarm occurs Warnin...

Page 42: ...changed using the and buttons The button moves to the next digit Pressing the button shows the programming menu Pressing the button again displays the most recently recorded event The event number eve...

Page 43: ...dition is removed before the programmed timer expires no alarm is raised Alarms can be configured as latching For a latching alarm the alarm will be displayed even if the fault condition is removed Al...

Page 44: ...d hold the and buttons for 5 seconds The following password prompt will be displayed upon entering program mode The 4 digit password must be entered using the and buttons Pressing the and buttons chan...

Page 45: ...go back to the main menu press and hold the button Within the group and buttons are used to navigate between program parameters Valid parameters are listed on the screen The selected parameter is hig...

Page 46: ...01 EN 47 In order to exit program mode press and hold the and buttons together for 5 seconds The controller exits the program mode automatically if there is no action after 2 minutes 19 4 EXITING PROG...

Page 47: ...tive 0 1 0 0 continuous 1 intermittent Alarm Event Record 0 1 1 0 Disabled 1 Enabled Warning Event Record 0 1 1 0 Disabled 1 Enabled Digital Input 1 Event Record 0 1 1 0 Disabled 1 Enabled Digital Inp...

Page 48: ...ked Voltage Fault Delay Sec 0 255 30 If phase voltages are outside the limits for this duration the unit concludes that mains power is faulty Voltage Alarm Latching 0 1 1 0 non latching 1 latching Low...

Page 49: ...limit an alarm occurs If this value is set to 0 the alarm is not checked PF Alarm Timer Sec 0 255 30 If the PF of any channel is outside the limits for this duration an alarm occurs Overcurrent Alarm...

Page 50: ...0 50 0 If current unbalance exceeds his value an alarm occurs If this value is set to 0 the alarm is not checked Current unbalance is calculated as the maximum deviation from the average Current Unba...

Page 51: ...er 0 1 10 The duration between receiving a fault signal and raising the alarm Contact Type 0 1 0 Normally open 1 Normally closed Input Function 0 99 Selected from list of pre defined input functions A...

Page 52: ...uctive reactive alarm 22 Reactive power alarm 23 Capacitive PF alarm 24 Inductive PF alarm 25 PF alarm 26 High current alarm 27 THD V alarm 28 THD I alarm 29 THD alarm 30 Voltage unbalance alarm No De...

Page 53: ...ns which can be assigned to analog outputs are listed below The unit offers 3 analog outputs which can be programmed with their desired minimum and maximum values according to the list below OUTPUT FU...

Page 54: ...character size with the and buttons and press the button 2 Select the parameter to be displayed on screen from the Select an Item menu and press the button For the next item return to the character si...

Page 55: ...lue is displayed on the bottom right of the screen and press to record the calibration and return to PROGRAMMING mode The battery supplied real time clock in the device is configured with these parame...

Page 56: ...mation in degrees Turkish cities are available as a table for ease of use NOTE For latitudes within the polar circles sunset and sunrise are not calculated Longitude Degrees 180W 180E 36 444E This par...

Page 57: ...ress and hold the button to return to programming Function Configuration Screen The controller offers 2 levels of negative component overcurrent protection each with its own distinct parameter group P...

Page 58: ...automatic reclosure function which enables the system to reclose if all the faults are corrected after a successful breaker trip The number of trials delay timers for each trial and the decision peri...

Page 59: ...level 1 protection I 1 Current Setting In 0 08 4 00 1 50 Current threshold for level 1 protection I 1 Delay Timer Sec 0 00 100 00 1 00 Constant time delay for level 1 protection I 1 TMS 0 025 1 200 1...

Page 60: ...r to MODBUS COMMUNICATION section The internal records can be read and saved to a PC via Rainbow Plus software The records are composed of the following values Record date time Status of digital input...

Page 61: ...sing the baud rate provides faster communication at a shorter communication distance Decreasing the baud rate allows communication at longer distances with a slower rate of data transmission 9600 baud...

Page 62: ...r of Registers Top 0 5 Number of Registers Bottom Max 7Bh 123 decimal 6 CRC Bottom Byte CRC calculation is explained below in detail 7 CRC Top Byte CRC calculation is explained below in detail An exam...

Page 63: ...ddresses are listed below 4 Data Top Byte 5 Data Bottom Byte 6 CRC Bottom Byte CRC calculation is explained below 7 CRC Top Byte CRC calculation is explained below An example message is given below wh...

Page 64: ...h the bottom byte The final CRC value that must be calculated by the algorithm is shown below 01 03 00 20 00 10 45 CC 01 06 00 40 00 10 89 D2 The unit has 15000 records of 64 bytes each in its 1MB mem...

Page 65: ...21 V_supply Device Power Supply 16 BIT R O Unsigned word x10 22 S_tot S VT Ratio CT Ratio 16 BIT R O Unsigned word x1 23 Cos_tot Power Factor 16 BIT R O Unsigned word x1000 24 I_neut Neutral Current C...

Page 66: ...Write kWh1 import counter value 16 BIT W O Unsigned word x1 16393 kWh1 e Write kWh1 export counter value 16 BIT W O Unsigned word x1 16394 kVArh1 i Write kVArh1 inductive counter value 16 BIT W O Uns...

Page 67: ...R O Signed long x1000 REGISTER ADDRESS VARIABLE DESCRIPTION SIZE R W TYPE X 12288 kWh1_I kWh1_import counter value 32 BIT R O Unsigned long x10 12290 kWh1_E kWh1_export counter value 32 BIT R O Unsig...

Page 68: ...ctive Power kVAr 32 BIT R O Signed long x100 20512 Q2 Phase 2 Reactive Power kVAr 32 BIT R O Signed long x100 20514 Q3 Phase 3 Reactive Power kVAr 32 BIT R O Signed long x100 20516 Q Total Reactive Po...

Page 69: ...O Unsigned word x1 21159 Event_No Current Event Number 16 BIT R O Unsigned word x1 21160 Reset_sta Last Reset Cause 16 BIT R O 16 bit bitmap 21161 Topology Topology 16 BIT R O Unsigned word x1 21162...

Page 70: ...tion 7 Low kVar 23 Reverse Direction Overcurrent Protection 8 High Cos 24 Broken Conductor Protection AUX 9 Low Cos 25 Earth Fault Protection AUX 10 High Current 26 High Precision Earth Fault Protecti...

Page 71: ...long 10 12348 Min_U23 Minimum U23 32 BIT R O unsigned long 10 12350 Min_U31 Minimum U31 32 BIT R O unsigned long 10 12352 Min_I1 Minimum I1 32 BIT R O unsigned long 10 12354 Min_I2 Minimum I2 32 BIT...

Page 72: ...uropean Parliament and of the Council of 27 January 2003 on waste electrical and electronic equipment WEEE this unit should be stored and disposed separately from usual waste The unit is compliant to...

Reviews: