DPR-165 User Manual                                                                      V-1.4 

(01.07.2015) 

 

-1- 

 

  

 

  

DPR-165  

TRANSFORMER STEP & 
TEMPERATURE 
INDICATOR 

 

    

 

 

 

DPR-165 is a microprocessor controlled precision 
instrument displaying steps and temperatures of 
MV/HV transformers. The unit has a high degree 
of protection against electromagnetic noises. 

The unit determines the step by measuring the 
resistive converter of the transformer. 

The step information is displayed on the screen. 
Additionally it is output through the 4-20mA 
analog output. This information may be fed to 
automation systems or to the next DPR-165 unit. 

It can also display the step information from the 
analog value coming from another DPR-165 unit. 

With analog inputs and outputs, an unlimited 
number of DPR-165 units may be cascaded. 

The unit offers one PT100 type temperature 
sensor input. This input may be used for the 
transformer or ambient temperature. The alarm 
level of the temperature input is adjustable and 
the alarm information is output as a relay contact. 

The unit offers an adjustable cable length 
compensation function in order to have precise 
measurements with long cables. 

The unit offers 2 volt-free relay contacts rated 6A. 
Any function may be assigned to these outputs, 
selected from list. 

Alarm levels are adjusted within the programming 
mode of the unit. If no action is taken, the unit will 
terminate the programming mode in 1 minute. 

The standard isolated RS-485 Modbus RTU port 
of the unit is free from ground potential 
differences and allows safe transfer of information 
to automation and monitoring systems. 

The supply inputs of the unit is isolated from 
measurement inputs. It operates between 88-
400VDC and 85-270VAC. 

 

Up to 50 steps 

Installation without energy interruption 

Accurate step measurement input, 10 bit 

16 bit analog output accuracy 

10 bit analog input accuracy 

PT100 temperature input, 1

°C accuracy 

Cable length compensation 

Automatic sensor failure detection 

2 relay outputs, 6A/250Vac 

Fully isolated RS-485 serial port 

MODBUS-RTU communications 

Logging of maximum temperature 

Front panel adjustable parameters 

Temperature alarm threshold level 

Easy to read, 4 digits 14mm led display 

Minimum 20 years data retension 

Wide supply range: 88-400 VDC (85-270VAC) 

Low panel depth, easy installation 

Wide operating temp. range, -

20...+70°C 

Sealed front panel (IP65 with gasket) 

Two part connection system

 

 

  

 

   

 

 

DESCRIPTION

 

FEATURES

 

Summary of Contents for DPR-165

Page 1: ...th long cables The unit offers 2 volt free relay contacts rated 6A Any function may be assigned to these outputs selected from list Alarm levels are adjusted within the programming mode of the unit If...

Page 2: ...anty voids if the unit is open Fuse must be connected to the power supply input Fuses must be of fast type FF with a maximum rating of 6A Disconnect all power before working on equipment When the unit...

Page 3: ...ISPLAYS 3 1 DISPLAY NAVIGATION 4 ALARMS 4 1 ALARM MENU 5 PROGRAMMING 5 1 ENTERING THE PROGRAMMING MODE 5 2 LAMP TEST 5 3 RELAY TEST 5 4 PROGRAM PARAMETER LIST 5 5 AUTO SETUP AND TRANSFORMER STEP TEMPE...

Page 4: ...ning Make electrical connections with plugs removed from sockets then place plugs to their sockets Otherwise sockets may get damaged Make sure not overloading relay outputs Use additional contactors i...

Page 5: ...DPR 165 User Manual V 1 4 01 07 2015 5 Panel Cutout Required Panel Depth 1 1 FRONT REAR PANELS 1 2 MECHANICAL INSTALLATION...

Page 6: ...er supply input in close proximity of the unit Fuses must be of fast type FF with a maximum rating of 6A Use cables of appropriate temperature range Use adequate cable section at least 0 75mm2 AWG18 F...

Page 7: ...DPR 165 User Manual V 1 4 01 07 2015 7 1 4 INSTALLATION DIAGRAM...

Page 8: ...splays alarm menu if there is any alarm Increase related value configuration mode Decrease related value configuration mode HELD PRESSED FOR 5 SEC Clears alarms HELD PRESSED FOR 5 SEC Resets Maximum T...

Page 9: ...ode button allow navigation between measurement values Leds related to the currently displayed values will turn on other leds will turn off STP Displays the step by measuring the resistive converter o...

Page 10: ...off and normal operating mode will be resumed ALARM CODE DESCRIPTION SHORT CIRCUIT Indicates a short circuit on the related channel Cables should be checked OPEN CIRCUIT Indicates a missing connection...

Page 11: ...eters may be scrolled with Mode button Related parameter name is displayed When Mode button is pressed for 5 seconds the parameter value is displayed Parameter values are modified with up and down but...

Page 12: ...screen Down button deactivates the relay output and displays 0 on the screen Mode button will select the next relay output or parameter value 5 2 LAMP TEST When exiting the PROGRAM mode the unit makes...

Page 13: ...led 1 enabled 0 1 MULTIPLE RESISTIVE STEP PARAMETER It is the parameter to set the step with multiple resistive value It must be 0 if there is no any step with multiple resistive value 0 50 ALARM ENAB...

Page 14: ...LARM ENABLE PARAMETER It is the parameter to enable PT100 temperature protection 0 disabled 1 enabled 0 1 0 20 4 20 ma ANALOG INPUT ALARM ENABLE It is the parameter to enable alarm function of 0 20 4...

Page 15: ...ll turn off if value is set 0 0 1 MODBUS NODE ADDRESS This parameter defines the address of the unit in a Modbus network Each device in the same network must have a different address 1 240 MODBUS BAUD...

Page 16: ...e button and the next parameter is displayed Select PtCA cable section parameter to enable PT100 calibration and hold Mode button for 5 seconds Enter PT100 cable section mm2 The value on the screen is...

Page 17: ...th Mode button and step led will flash for 10 seconds Calibration process is completed for step 1 It will display 2 on the screen to calibrate step 2 The same operations continue until the last step i...

Page 18: ...ammable relay output may be selected from the below list Value Relay Function 0 PT100 Over Temperature 1 PT100 Open Circuit 2 POT 1 Open Circuit 3 POT 2 Open Circuit 4 PT100 Short Circuit 5 POT 1 Shor...

Page 19: ...tructure contain multiple registers Detailed description about the MODBUS protocol is found in the document Modicon Modbus Protocol Reference Guide This document may be downloaded at www modbus org do...

Page 20: ...BIT R W unsigned word 1 6 Cable length PT100 Cable length 16 BIT R W unsigned word 1 7 Cable section PT100 cable section 16 BIT R W unsigned word 0 01 8 Temperature PT100 alarm limit 16 BIT R W unsig...

Page 21: ...DDRESS KAYIT BIT R W DESCRIPTION 20488 0 R O High temperature relay status 1 R O PT100 open circuit relay status 2 R O Pot1 open circuit relay status 3 R O Pot2 open circuit relay status 4 R O PT100 s...

Page 22: ...Analog output mA value of analog output 16 BIT R O unsigned word 0 01 20484 Analog input mA value of analog input 16 BIT R O unsigned word 1 20485 Step value from analog Step value from analog input 1...

Page 23: ...l Type RS 485 Communication Modbus RTU Data Rate 2400 115200baud Isolation 1000V AC 1 minute Operating Temp Range 20 C 70 C Max Relative Humidity 95 non condensing IP Protection IP 65 front panel with...

Reviews: