Although the unit is protected against 
electromagnetic disturbance, excessive 
disturbance can affect the operation, 
measurement precision and data 
communication quality. 

 

Use cables of appropriate temperature 

range. 

 

Use adequate cable section, at least 

0.75mm

(AWG18).  

 

For current transformer inputs, use at 

least 1.5mm

2

 section (AWG15) cable. 

 

The current transformer cable length 

should not exceed 1.5 meters. If longer 
cable is used, increase the cable section 
proportionally. 

 

Current transformers must have 5A 

output. 

 

For the RS-485 connection, use 

appropriate shielded twisted wire cable. 
Communication quality will depend 
highly on the cable used. 

 

 

 

 

 

 

 

 

Three buttons on the front panel provide 
access to configuration and measurement 
screens.  

BUTTON 

FUNCTION 

 

Selects next display group. 

Press and hold for 3 
seconds: 

Removes alarms. 

 

Selects next display screen 
in the same display group. 

 

Selects previous display 
screen in the same display 
group.  

Press and hold for 10 
seconds:

 

Current screen will be the 
default display screen 

 

Press and hold for 3 
seconds: 

Enable programming mode. 

 

 

REQUIRED PANEL DEPTH 

 

PUSHBUTTON FUNCTIONS 

 

 

Do not install the unit close 
to high electromagnetic 
noise emitting devices like 
contactors, high current 
busbars, switchmode 
power supplies and the 
like.

 

 

ELECTRICAL INSTALLATION 

 