Model 1221 with
Oscillation Indication
DAS Public Safety
Annunciator Panel
Installation Instructions
12/01/2023
[email protected]
Technical Support
ph: 303 526 1965
8:am - 5:pm (Mountain)
Page 1: ...Model 1221 with Oscillation Indication DAS Public Safety Annunciator Panel Installation Instructions 12 01 2023 sales dasalert com Technical Support ph 303 526 1965 8 am 5 pm Mountain...
Page 2: ...Self Test 5 Buzzer Alarm 5 DC Power for the Panel 5 Wiring Options 6 10 DIP Switch Settings 11 12 Panel AA Battery Backup 13 Connections to Building s Fire Panel 14 Removal of Knockouts 14 Relay and...
Page 3: ...gure 5 Wiring Digram with one CAT 5 6 Cable 9 Figure 6 Wiring Diagram for one CAT 5 6 Cable 10 Where there are no System Components and no Oscillation Indication Required Figure 7 Relay and End of Lin...
Page 4: ...ting pad 2 Key 1 Wall Mount Drill Template 3 Knockout Plugs 1 Instructions Compatibility This annunciator panel meets or exceeds all UL 2524 IFC NFPA and Local Requirements It is functionally backward...
Page 5: ...Figure 1 Included Items 2...
Page 6: ...3 Figure 2 Connector and DIP Switch Locations...
Page 7: ...ms the specific alarm LED will designate the problem by turning RED The Push to Test Button on the panel s front illuminates all of the LEDs Unlike previous versions of the Model 1221 it does not actu...
Page 8: ...ich has an audible alarm triggered by the DAS alarms then the DASAlert buzzer can be permanently disabled by setting DIP switch SW 2 switch 9 to the ON position If the key is lost contact Technical Su...
Page 9: ...les from the DAS equipment to the Panel is another variable If the cables are shorter than 20 feet then no End of Line Resistors EOLR are required by code to supervise the connections The location of...
Page 10: ...Figure 3 Wiring Diagram if cable length is less than 20 feet set switches 1 8 to ON on DIP Switch SW1 7 DASalert Model 1221 in Fire Command Center Donor Antenna Disconnected Donor Antenna Disconnected...
Page 11: ...g Diagram with two CAT 5 6 cables if cable length is greater than 20 feet set switches 1 8 to OFF on DIP Switch SW1 8 Donor Antenna Disconnected Donor Antenna Disconnected DASalert Model 1221 in Fire...
Page 12: ...nnected Donor Antenna Disconnected DASalert Model 1221 in Fire Command Center Figure 5 Wiring Diagram with one CAT 5 6 cable set switches 1 8 to OFF on DIP Switch SW1 DC power supply located in Fire C...
Page 13: ...ble for installations where there are no System Components and no Oscillation Indication required Set all switches on SW1 to OFF except 7 and 8 10 Donor Antenna Disconnected Donor Antenna Disconnected...
Page 14: ...ctory Default OFF 3 Donor Antenna Trouble Factory Default OFF 4 Charger Trouble Factory Default OFF 5 Battery Low Factory Default OFF 6 Donor Antenna Disconnected Factory Default OFF 7 Other System Co...
Page 15: ...Table 3 Factory Default DIP Switch Settings Table 4 Fire Panel Relays 12...
Page 16: ...a preset level Once the batteries reach this level it typically requires 24 hours to recharge If the batteries are not installed or are drained an alarm is generated indicating Panel trouble An indic...
Page 17: ...ed shorted indicating an alarm condition The single pole relays are rated for a max current of 200 ma and 30 Volts DC If these values are exceeded self resetting fuses in series with the relay contact...
Page 18: ...Figure 7 Relay and End of Line Resistor Connections ELOR to Fire Panel 15 Comm Trouble From J5 on Main PCB ELOR on J6 Comm Trouble From J5 on Main PCB ELOR on J6...
Page 19: ...or donor antenna is disconnected an alarm should be triggered In the event that the BDA in use does not sense this condition to output an alarm relay closure an external method using a bias T can be c...
Page 20: ...17 Specifications...
Page 21: ...18 Specifications Continued...