13
Test facility
Drawing
This drawing illustrates the control panel with the test button:
Test
Test
When activating the test button the unit starts the 5-step-test program. The unit will run
through the different tests according to the below table.
The fail LED will operate normally indicating fail if and when detected.
If any fail is detected during the test, the LED will flash with a frequency of 1 Hz for 30
seconds after the test is done to indicate some fault were detected.
The table below describes what is checked during the test.
Test point
Heater
Damper
Internal fan
LED
Duration
1 Off
Closing
Stopped
Jingle 30
sec.
2 On
Closing
Idle
Normal
35
sec.
3 Off
Opening
Medium
Normal
40
sec.
4 Off
Closing
High
Normal
35
sec.
5 Off
Closing
Idle
Normal
30
sec.