34
Technical Data
Specification
Abbr . Unit
HCV 400
P1
HCV 400
P2
HCV 400
E1
Operating range (min . -
max . @100Pa)
m3/h
80 to 250
60 to 240
60 to 240
Nominal flow (@100Pa)
V
NOM
m 3/h
150
Reference flow (@50Pa)
V
REF
m 3/h
175
168
Performance
Thermal efficiency EN13141-
7 dry at reference flow
h
SUP
%
93,2
89
81
Specific power input at
reference flow
SPI
W/(m
3/h)
0,23
0,19
0,2
Filters according to EN779
(extract/outdoor)
class
-
G4/G4 (F7 optional)
Installation surrounding
temperature
t
SURR
°C
from +12 to +50
Outdoor temperature with-
out preheater installed
t
ODA
°C
from -12 to +50
Outdoor temperature with
preheater installed
t
ODA
°C
from -25 to +50
Max . absolute humidity in
extract air
x
g/kg
10
Cabinet:
Dimensions (without floor
console, incl . 12 mm wall
bracket)
W x H
x D
mm
540 x 1056 x 561
Spigots / Duct connections
Ø
mm
160 - female
Weight
m
kg
39
40
Heat conductivity of the
polystyrene insulation
l
W/(mK)
0,031
Heat transfer coefficient of
the polystyrene insulation
U
W/
(m
2
K)
<1
Fire classification of the
polystyrene insulation
class
-
DIN 4102-1 class B2; EN 13501 class E
Drainage hose included
Ø/
length " / m
3/4” - 1m
Cabinet colour
RAL
-
9016
Electrical
Voltage
U
V
230
Max . power consumption
(without/with preheater)
P
W
170/1570
Frequency
f
Hz
50
IP-class
class -
21