Dantherm DFC 350 Service Manual Download Page 1

Focus. Trust. Initiative.

Summary of Contents for DFC 350

Page 1: ...Focus Trust Initiative...

Page 2: ...2005 layout...

Page 3: ...DFC 350 and 450 Service manual EN No 840121 rev 1 3 09 01 2012...

Page 4: ...hold for trykfejl og ndringer Dantherm can accept no responsibility for possible errors and changes Irrt mer und nderungen vorbehalten Dantherm n assume aucune responsabilit pour erreurs et modificati...

Page 5: ...e of content The Service Manual covers the following main topics Topic See page General information 4 General principle for DFC units 5 Parts and function 6 How to mount the DFC 350 and DFC 450 7 Tech...

Page 6: ...roducts The Service Manual cover the following products Name Type No DFC 350 299763 DFC 450 299745 Copyright Copying of this service manual or part of it is not allowed without written permission from...

Page 7: ...much on the circulation of the internal air circulation in the telecom equipment and in the shelter It is therefore very necessary to do a thorough test of the airflows in the shelter before initiatin...

Page 8: ...on Part Description Filter guard Measures the pressure on both sides of the filter When the pressure drop exceeds 150 Pascal factory setting the build in switch which is connected to the controller wi...

Page 9: ...ep Action 1 Make a 245mm hole in the shelter wall about 1900 mm above the floor 2 Demount the front cover of the unit by removing the 3 fluted grip knobs 3 Hold the unit in position and fasten it to t...

Page 10: ...ng rubber on the flanges of the hood hold it in position above the inlet hole and fasten it to the wall Exhaust damper Cut out an exhaust opening W 1000xH 210mm above the door when possible Hold the m...

Page 11: ...position and fasten it to the wall Ground Connect the DFC 450 to ground by using the nut market with ground symbol For more wiring information please see section Wiring Diagram Electrical connec tion...

Page 12: ...35 W Sound pressure at 5m from shelter 36 dB A 34 dB A Sound pressure at 10m from shelter 31 dB A 31 dB A Cabinet This table shows the specifications for the cabinet Specification Designation DFC 350...

Page 13: ...ng table Specification Designation DFC 450 Weight Controller excluded 13 kg Metal sheet material Aluzinc AZ150 0 8 1 5 mm Fan motor Data of the fan motor is shown in the following table Voltage versio...

Page 14: ...C Enclosure IP65 DIN rail mounting Enclosure IP65 Standard control units See separate manu als ACUE 3000 TKS 3000 EC Special control units See separate manu als FAC 48 Indoor temperature sensor RG TD5...

Page 15: ...kW t 5 C Cooling performance is calculated from outdoor temperature and indside temperature in 1 6m height Fan working range 15 to 50 DFC 350 Airflow Pressure drop 0 20 40 60 80 100 120 140 160 180 2...

Page 16: ...ow Pressure drop The diagram below shows data for DFC 450 DFC 450 Airflow Pressure drop 0 20 40 60 80 100 120 20 30 40 50 70 100 Fan speed Pressure drop Pa 0 200 400 600 800 1000 1200 1400 1600 Airflo...

Page 17: ...15 840121 Version 1 3 09 01 2012 Dimensions Illustration DFC 350The drawings below illustrate the dimensions of the DFC 350 Continued overleaf HOLE CUT OUT DIMENSION 245...

Page 18: ...16 Dimensions continued Illustration DFC 450The drawings below illustrate the dimensions of the DFC 450 Continued overleaf HOLE CUT OUT DIMENSION 305...

Page 19: ...ions continued External ac cessories Air inlet hood with net 940 60299654 Exhaust air rain hood FC1100x220 940 30205576 Motorized Exhaust air damper SP1000x211 48VDC 940 02130724 230V DC 940 02130230...

Page 20: ...elow shows the three ways the Displacement Free Cooling unit can be mounted and still make filter exchange easy There are three different lids of which on ly one should be opened to take out and repla...

Page 21: ...x 1 5 3 ACUE 3000 DFC 101112 White Brown Indoor temp Sensor RG TD5A White Brown 2 x 0 25 1 2 Inlet and exhaust Air damper LM24 KTA 3 x 0 5 3 2 3 1 2 Red 3 White 1 Black Junction box 2 Brown Blue Yell...

Page 22: ...20 Wiring diagram TKS 3000A EC...

Page 23: ...ERATURE SENSOR UG TD5A FILTER ALARM NC NO ADJUSTABLE FAN ALARM NC NO ADJUSTABLE LOW TEMP ALARM NC NO ADJUSTABLE HIGH TEMP ALARM NC NO ADJUSTABLE PE N L HEATER AC START CIRCUIT 12V DC 12V DC DATA COMMU...

Page 24: ...that the site and unit is examined closely during the first preventive maintenance to determine whether the interval is too long We recommend that preventive maintenance visits are carried out during...

Page 25: ...entrifugal fan 230V AC 840061 Control parts This table shows the various control parts sensors and filter monitor for both the DFC 350 and DFC 450 Check the label on the controller for identification...

Page 26: ...r 7 function 6 ground 9 hole 7 indoor temperature sensor 12 installation 18 interval 22 maintenance 22 motorized damper 8 mount 7 outdoor temperature sensor 12 performance 13 power consumption 10 11 p...

Page 27: ...2005 layout...

Page 28: ...614 3700 Fax 45 9614 3800 E mail dantherm dk dantherm com www dantherm air handling com COMPANIES DENMARK Dantherm Air Handling A S Marienlystvej 65 DK 7800 Skive Denmark Tel 45 9614 3700 Fax 45 9614...

Reviews: