12
of 53
This illustration is showing the control strategies based on the default settings.
Action
Temperature
sensor
℃
UP
Down
℃
Temperature
sensor
Action
Condenser
fan speed
increased
to maxi-
mum
(around
2650RPM)
Condenser
sensor
60
60
Condenser
sensor
-
-
Condenser
sensor
57
57
Condenser
sensor
Condenser fan
speed
decreased to
medium
(around
2250RPM)
Condenser
fan speed
increased
to medium
(around
2250RPM)
Condenser
sensor
50
50
Condenser
sensor
-
-
Condenser
sensor
47
47
Condenser
sensor
Condenser
fan
speed
decreased
to low
(around
1850RPM)
Compres-
sor on
damper
closes
condenser
fan speed
low
(around
1850RPM)
Return sensor
(default
active cooling
set point)
35
35
Return sensor
Compressor on
damper closes
condenser fan
speed low
(around
1850RPM)