Operation
: Home menu level
Alarm status shows, which alarms are present currently (historical alarms are not
visible).
•
Only alarms that are mapped to any of the 10 hardware alarm outputs are vis-
ible in this menu. (see also “Sub-menu: Alarm config. level” on page 31)
List of available alarms:
•
Low volt (DC supply)
•
Onboard (temperature) sensor
•
High volt (DC supply)
•
Indoor (temperature) sensor
•
Temp low (low indoor temperature)
•
Hotspot (temperature) sensor
•
Temp high 1
(high indoor temperature level 1)
•
Ambient 1 sensor
(outdoor temperature sensor 1)
•
Temp high 2
(high indoor temperature level 2)
•
Ambient 2 sensor
(outdoor temperature sensor 2)
•
Temp high 3
(high indoor temperature level 3)
•
Digital (input) 1
•
Digital (input) 2
•
Humidity low (low indoor humidity)
•
Digital (input) 3
•
Humidity high (high indoor humidity)
•
Filter guard 1 (Standard)
•
Filter flow 1 - filter pressure level 1
(analog pressure sensor optional)
•
Filter guard 2 (Standard)
•
Network (LAN connection)
•
Filter flow 2 - filter pressure level 2
(analog pressure sensor optional)
•
Memory (Internal non volatile memory)
•
SD card (Read/write failure)
•
Fan 1
•
Fan 2
This override mode can be used by service personnel to obtain a suitable tem-
perature in shelter during service job (duration can be changed).
•
The controller will automatically return back to normal operation strategy,
when time (defined via settings) has passed.
•
Free cooling fan is limited to idle RPM.
List of settings:
•
Set point °C (10-30 °C)
•
Duration in minutes. (maximum 480 minutes)
•
Disable/enable
Alarm status
Occupied mode
en