19
Installation
: External Connections
The terminal rail J.5 is to be used for connecting other accessory as e.g. a fire/smoke alarm or
door switch.
•
Terminal type: FCI 20020110-C061A01LF (Mating type Anytek KD0610500000G).
Pin J .5
Digital 1-3
Cable type
1
DIG 1 (1K pull up to 12 V DC)
0,5 mm
2
2
GND
3
DIG 2 (1K pull up to 12 V DC)
4
GND
5
DIG 1 (1K pull up to 12 V DC)
6
GND
The terminal rail J.11 is to be used for connecting one or two temperature sensors.
The terminal rail J.35 is to be used for connecting a humidity sensor.
•
Terminal type: Anytek KE081151A000G (Mating type Anytek KD081050A000G).
Pin J .11
T . sensor
J .35
I2C Comm . (humidity sensor)
Cable type
1
Room temp. sensor (NTC type)
+3,3 V DC
0,5 mm
2
2
GND
SCL
3
Hotspot temperature sensor (NTC type) SDA
4
GND
GND
The terminal rail J.38 is to be used for connecting a heater.
The terminal rail J.15 is to be used for connecting other equipment using 24 V DC.
•
Terminal type: Anytek KE061151A000G (Mating type Anytek KD061050A000G).
Pin J .38
Heater
J .15
24 V DC
Cable type
1
Heat/ +24 V
Output can be configured as dry contact or 0/24 V DC
output, set jumper on PCB (see page 14).
24 V DC 100mA
0,5 mm
2
2
Heat - 0/24 V DC
NC
3
GND
GND
J17 is a RJ45 LAN connector CAT5/CAT6 . PulseJack J00011D21BNL
Digital input
(Fig . 11)
Temp . sensor/
I
2
C Comm .
(humidity sensor)
(Fig . 11)
Heater/
24 V DC AUX
(Fig . 11)
Ethernet
(Fig . 11)