6. MOUNTING OF UNIT TO ENCLOSURE & OPERATION

The enclosure shall be checked for correctness of cutouts, mounting holes and
electrical supply.

The 

Mounting Hook

 is preset to match the recommended cutout openings.  If an

adjustment other than the factory setting of the hook needs to be made, do so prior
to fixing the gasket to the Heat Exchanger.

Install the gaskets as shown in section 5.1.  A gasket kit is provided with each
unit. (Not required for PS018XXX-XX)

Remove the outer cover of the Heat Exchanger by removing the screws from
either the side or bottom of the unit.  Depending on options selected, use a #2
Phillips Screwdriver, #20 Torx driver, or #15 Security Torx with pin driver.  All
screw threads are M4.

Utilize an appropriate and safe lifting device.

Mount the Heat Exchanger to the cabinet by using the mounting hook, which
supports the weight of the unit.  The hook grabs the cut out opening on the cabinet
panel.

Install the mounting hardware as supplied with the unit (M6 x 25 SCKT HD cap
screws & washers). The fixings are installed from inside the cabinet into the
threaded inserts located in the unit.  Use 4mm Allen wrench / driver.

For PS018XXX-XX:

Place the unit for the inside of shelter through cutout opening using an appropriate
and safe lifting device.

Connect the Heat Exchanger power lead to the mains supply located in the
cabinet/enclosure. 

Refer to the product label on the bottom right hand side panel

of the unit for the proper voltage/amp requirement.  Make sure a properly
grounded power supply is used. All installations are to be completed in
accordance with local NEC codes and guidelines.

The electrical circuit should be protected by a slow blow breaker or fuse.  Refer to
section 5 in this manual for fuse/breaker rating.

After final installation and power supply connection the unit should powered and
the unit checked for correct airflow.

For PS0XX0XX-XX-S (Speed Control)

Push and hold test button located on control board for 5 seconds, to activate the
self test.

Check to correct airflow and fan speeds.

Please contact Dantherm for more information if required.

Dantherm

 Cooling 

, Inc. Heat Exchanger Operating & Maintenance Manual 

HexFlow Pinnacle Series Product Information Manual  

Summary of Contents for HEXFLOW PINNACLE Series

Page 1: ...OW Pinnacle Series Heat Exchangers Product Information Manual Last Revised June 11 2019 Rev A 864 595 9800 tech support danthermcooling com 110 Corporate Drive Spartanburg SC 29303 www danthermcooling...

Page 2: ...ge 2 of 14 Contents 1 GENERAL SAFETY WARNING INSTRUCTIONS 3 2 UNPACKING HANDLING INITIAL INSPECTION 3 3 MODEL IDENTIFICATION 4 4 OPTIONS 4 5 PRODUCT DRAWINGS 5 6 MOUNTING OF UNIT TO ENCLOSURE OPERATIO...

Page 3: ...g hardware is firmly secured before leaving installation All cable and connectors must conform to UL standards The heat exchanger is UL recognized and tested to UL1995 It will comply where necessary w...

Page 4: ...erature decrease below 60F will cause the fan to be turned off between the range of 60F 80F the fan will be operating based on the pervious environmental condition experienced Pinnacle S Standard X Cu...

Page 5: ...nting Flange Installation Gasket Cabinet Air OUT Cabinet Air IN Installation Gasket Mounting Hook Cabinet Air IN Ambient Air OUT Ambient Air IN Cabinet Air OUT Dantherm Cooling Inc Heat Exchanger Oper...

Page 6: ...Diagrams 5 2 1 PS018XXX XX series 5 2 2 Cut Out Mounting Information for older PS023011 017 022 XX series prior to 2008 Dantherm Cooling Inc Heat Exchanger Operating Maintenance Manual HexFlow Pinnac...

Page 7: ...Mounting Information PS023011 017 022 XX series 2008 on 5 2 4 Cut Out Mounting Information PS023026 XX series Dantherm Cooling Inc Heat Exchanger Operating Maintenance Manual HexFlow Pinnacle Series...

Page 8: ...Cut Out Mounting Information PS035XXX XX series 5 2 6 Cut Out Mounting Information PS060XXX XX series Dantherm Cooling Inc Heat Exchanger Operating Maintenance Manual HexFlow Pinnacle Series Product...

Page 9: ...screws washers The fixings are installed from inside the cabinet into the threaded inserts located in the unit Use 4mm Allen wrench driver For PS018XXX XX Place the unit for the inside of shelter thro...

Page 10: ...1 PS060100B 100 230VAC 50 60 1 1 1 5 135 62 The information provided above is a general overview for reference only The customer is responsible for the correct installation and application of each pro...

Page 11: ...am All Models 11 17 22 35 45 55 100 A B 8 1 2 DC Voltage Diagram All Models 11 17 22 35 45 55 Y Z without speed control Dantherm Cooling Inc Heat Exchanger Operating Maintenance Manual HexFlow Pinnacl...

Page 12: ...with HX2 Speed Control up to batch date 130601 8 1 4 DC Voltage Diagram PS0XX0 11 17 22 35 45 55 Y Z with HX2 Speed Control Batch date 130601 and newer Dantherm Cooling Inc Heat Exchanger Operating Ma...

Page 13: ...proper installation misuse of the product negligent servicing improper applications unauthorized modifications improper electrical supply failure to follow manufacturer s instructions and rating plate...

Page 14: ...Number of units requested to be returned Reason for return Contact name phone and fax number Date of product receipt Invoice number and purchase order number covering the unit s The customer is respo...

Reviews: