Installation notes
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
E-mail: [email protected]
Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products
Please call for more information or a free catalogue, or visit our website.
This product conforms to BS EN 60669-2-1.
Please ensure the most recent edition of the appropriate local wiring regulations are observed
and suitable protection is provided e.g. 6 amps over current, 1kV over voltage. Please ensure
that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Precautions and Warranty
Grid time lag switches (3-wire versions)
GRTLA MK
GRTLA CB
GRTLA EU
GRTLA MK ILM
GRTLA CB ILM
GRTLA EU ILM
DANLERS grid time lag switches are suitable for fitting into the MK
Grid Plus (MK), Crabtree grid (CB) and Eurodata plates (EU).
A short press will switch the load on and it will switch off automatically
after the time lag period has expired. The time lag can be set between
approximately 1 minute and 2 hours.
These devices need a neutral supply.
The button on the illuminated versions (ending ILM) is lit until the
button is pressed, it comes back on when the time lag has elapsed.
The load can be switched on from other locations by wiring these
devices in parallel.
DANLERS grid time lag switches can switch up to 6amps (1500W) of:
• Fluorescent lamp, either high frequency or switch start
• Incandescent or mains halogen lamps (recommended with integral safety fuse)
• Electronic or wire wound transformers
They can also switch up to:
• 1 amp (250W) of Fans or Metal Halide lamps.
The grid time lag switches need the following depth wall boxes:
• GRTLA MK (ILM)
35mm (minimum)
• GRTLA CB (ILM)
40mm (minimum)
• GRTLA EU (ILM)
35mm (minimum)
12/02/14
INS912 GRTLA
Loading
Cannot get a neutral supply to the switch:
• Consider using DANLERS 2-wire grid time lag.
Time lag switch “clicks” off but load stays on:
• Non-resistive load (contactor, emergency, CFL, LED or 2D lamp)
Add CAPLOAD across the load as shown in wiring diagram.
• Fault developed due to an over-voltage spike.
Load latched either on or off:
• Fault developed due to an over-voltage spike.
Grid wall box depths
Troubleshooting