Installation notes

DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.

Telephone: +44 (0)1249 443377   Fax: +44 (0)1249 443388   

E-mail: [email protected]    Web: 

www.danlers.co.uk

Company Registered Number 2570169   VAT Registration Number 543 5491 38

Products available from DANLERS

•  PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers 

•  Photocells • Radio remote controls • Time lag switches • Outdoor security switches 

•  Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products

Please call for more information or a free catalogue, or visit our website.

This product conforms to BS EN 60669-2-1.
Please ensure the most recent edition of the appropriate local wiring regulations are observed 

and suitable protection is provided e.g. 6 amps over current, 1kV over voltage. Please ensure 

that this device is disconnected from the supply if an insulation test is made. 
This product is covered by a warranty which extends to 5 years from the date of manufacture.

Precautions and Warranty 

  Grid time lag switches (2-wire versions)

  GRTL MK 

GRTL CB 

GRTL EU

  GRTL MK ILM 

GRTL CB ILM 

GRTL EU ILM

DANLERS grid time lag switches are suitable for fitting into the MK 

Grid Plus (MK), Crabtree grid (CB) and Eurodata plates (EU). 
A short press will switch the load on and it will switch off automatically 

after the time lag period has expired. The time lag can be set between 

approximately 1 minute and 2 hours.

The  button  on  the  illuminated  versions  (ending  ILM)  is  lit  until  the 

button is pressed, it comes back on when the time lag has elapsed.
The load can be switched on from other locations by connecting  these 

devices in parallel or by connecting DANLERS matching slave switches, 

available as: SSGS MK, SSGS CB and SSGS EU.

DANLERS grid time lag switches can switch up to 6amps (1500W) of:

•  Fluorescent lamps, either high frequency or switch start
•  Incandescent or mains halogen lamps

 (recommended with integral safety fuse)

•  Electronic or wire wound transformers. 

They can also switch up to:

•  1 amp (250W) of Fans or Metal Halide lamps.

 

The grid time lag switches need the following depth wall boxes:
•  GRTL MK (ILM)   

35mm (minimum)

 

•  GRTL CB (ILM)   

40mm (minimum)

 

•  GRTL EU (ILM)    

35mm (minimum)

12/02/14

INS911 GRTL

Loading

Time lag switch “clicks” off but load stays on: 

•  Non-resistive load (contactor, emergency, CFL, LED or 2D lamp)

 

   

Add CAPLOAD across the load as shown in wiring diagram.

 

•  Fault developed due to an over-voltage spike.

Slave switch does not operate the time lag switch: 

•  Ensure only DANLERS slave switches are used

 

•  Ensure slave wiring is less than 10m long.

Load latched either on or off: 

•  Fault developed due to on over-voltage spike.

Does not work with existing 2-way switches: 

•  Time lags and slaves can use the wiring of two way (and    

  intermediate) systems, but cannot be mixed with such systems.

Grid wall box depths

Troubleshooting