background image

Installation notes

DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.

Telephone: +44 (0)1249 443377   Fax: +44 (0)1249 443388   

E-mail: [email protected]    Web: 

www.danlers.co.uk

Company Registered Number 2570169   VAT Registration Number 543 5491 38

Products available from DANLERS

•  PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers 

•  Photocells • Radio remote controls • Time lag switches • Outdoor security switches 

•  Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products

Please call for more information or a free catalogue, or visit our website.

This product conforms to BS EN 60669-2-1.
Please ensure the most recent edition of the appropriate local wiring regulations are observed 

and suitable protection is provided e.g. 6 amps over current, 1kV over voltage. Please ensure 

that this device is disconnected from the supply if an insulation test is made. 
This product is covered by a warranty which extends to 5 years from the date of manufacture.

Precautions and Warranty 

  Ceiling Surface PIR occupancy switches

 

  CESF PIR IP66

DANLERS ceiling surface passive infra-red  occupancy switches (CESF 

PIR IP66) can be ceiling mounted on the square pattress box (PABO) 

supplied.

The CESF PIR IP66 incorporates a passive infra-red quad sensor to 

detect movement of a warm body within its detection zone (diagram 

A) and a photocell to monitor the ambient light level.
Upon detecting movement, if the ambient light is dark enough, the 

CESF PIR IP66 will switch the load on. The ambient threshold can 

be set by the user to between approximately 100 lux and infinite lux 

(photocell inactive) via the LUX adjuster (diagram B).
If no more movement is detected within a pre-selected time, then the 

CESF PIR IP66 will switch the load off. This time lag can be set via 

the TIME adjuster to 10 seconds, 20s, 40s, 1 minute 15 seconds, 

2m 30s, 5m, 10m, 20m or 40 minutes (diagram B).
CESF  PIR  IP66  also  incorporates  a  sensitivity  adjuster,  labelled 

‘SENS’, to reduce the range and sensitivity of detection (diagram B).

Loading

The CESF PIR IP66 can be connected to a 230V (+/-10%) 50Hz 

(+/-10%) ac supply
They can switch up to 6 amps (1500W) of:

 

•  Fluorescent lamps, high frequency or switch start

 

•  Incandescent or mains halogen lamps

 (recommended with integral safety fuse)

 

•  Electronic or wire wound transformers.

They can also switch up to:

•  2 amps (500W) of low energy lamps: CFL, LED, 2D etc.

 

•  1 amp (250W) of metal halide lamps or fans.
They have a minimum switching capacity of 0.5W, for less than this a Gold 

relay version should be used, see Variants section.
For larger loads, the PIR can be used to switch a contactor.

24/07/13

INSxxx CESF PIR IP66

Variants

As DANLERS design and manufacture in the UK, variants can be supplied, 

coded by the following suffixes and applied in this order:
•  12V or 24V   

12V or 24V (ac or dc) operation

 

•  VF   

 

Volt Free contacts

 

•  GOLD or LG 

Gold or Logic Gold contacts

 

•  NC   

 

Normally Closed contacts

Variant details are covered in an enclosed addendum sheet if applicable.

Troubleshooting

 

The load will not switch on:

 

•  The LUX adjuster is set too low and is inhibiting the switch.

 

•  The SENS adjuster is set too low.

 

•  The moving body is not emitting more IR than the background.

 

    (Person wearing insulating clothing in a warm environment)

 

•  Person is too far from the PIR switch, see detection diagram.

 

•  Person is moving unusually slowly (perhaps when testing).

The load switches on when nobody is present: 

•  Heater causing infra-red variations in a cold small room or ceiling void 

 

  drafts, fans, or sealed doors causing air movement.

 

    Reduce the sensitivity adjuster or consider using the 

 

    CESF PIR IP66 2D double detection version.

 

•  Please contact DANLERS for further technical support.