Installation notes

DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.

Telephone: +44 (0)1249 443377   Fax: +44 (0)1249 443388   

E-mail: [email protected]    Web: 

www.danlers.co.uk

Company Registered Number 2570169   VAT Registration Number 543 5491 38

Products available from DANLERS

•  PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers 

•  Photocells • Radio remote controls • Time lag switches • Outdoor security switches 

•  Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products

Please call for more information or a free catalogue, or visit our website.

This product conforms to BS EN 60669-2-1.
Please ensure the most recent edition of the appropriate local wiring regulations are observed 

and suitable protection is provided e.g. 6 amps over current, 1kV over voltage. Please ensure 

that this device is disconnected from the supply if an insulation test is made. 
This product is covered by a warranty which extends to 5 years from the date of manufacture.

Precautions and Warranty 

  Ceiling socket mounted photocell switches 

  CEPH NO 

CEPH RE

DANLERS ceiling socket mounting photocell switches can be plugged 

into  a  Klik-AX  lighting  socket  (DANLERS  order  codes:  CESO  or  

CESO SQ (diagram A).
When the ambient light level falls below the LUX threshold the photocell 

will switch the connected load on. It will switch the lights off again 

when the light level raises to approximately twice the LUX threshold, 

to avoid the possibility of ‘hunting’. 
The LUX threshold can be set by the user to between approximately 

100 and 1000 lux at the work surface by the LUX adjuster (diagram 

B). There is also an infinite lux setting where the lights will be switched 

on constantly. 
There  is  a  time  delay  of  approximately  a  minute  before  switching 

actually occurs, to avoid nuisance short term switching caused by a 

passing cloud etc. A small red LED changes state as soon as the LUX 

threshold is traversed to make set up easier.
The CEPH NO product will switch the lights on and off without user 

intervention. 

However with the CEPH RE, reset version, the load will 

only switch on again once a manual wall switch (wired before the 

photocell, diagram B) is switched off (for 5 seconds) and on again. 

Each time the manual wall switch (wired before either type of photocell)  

is switched, the lamp will switch on for 1 minute regardless of the 

ambient lux level.

Loading

These Photocell switches can switch up to 6 amps (1500W) of: 

•  Fluorescent lamps, high frequency or switch start 

•  Incandescent or mains halogen lamps

 (recommended with integral safety fuse) 

•  Electronic or wire wound transformers.

They can also switch up to: 

•  1 amp (250W) of fans or metal halide lamps.

21/01/11

INS931 CEPH

Troubleshooting

 

The load will not switch on with the CEPH RE

 

•  The manual wall switch must be turned off for about 5 seconds and  

  back on again to reset the photocell.

The load switches on and off every minute with the CEPH NO

 

•  Too much artificial light is entering the photocell.

The load switches off after a minute with the CEPH RE

 

•  Too much artificial light is entering the photocell.

The lights switch on too early, when it is light enough in the room

 

•  Rotate the LUX adjuster further clockwise, towards ‘-’.

The lights switch on too late, when it is already dark in the room

 

•  Rotate the LUX adjuster further anti-clockwise, towards ‘+’.