Controls Installation
Table 26
OEM Installed Connections
Cable Specifications
Rev C
Connector #
Label
Function
Description
J1
24VDC
CIM Power
24VDC from the CCM to CIM
J2 Pin 1, 2
Interlock
Drive Interlock
Safety interlock from the Drive, Open when drive is in fault
J2 Pin 3-5
Can Bus
CAN Communication
CAN Communication from the drive to the CIM
J3 Pin 1, 2
Interlock
Interlock
Digital input from PLC without voltage supply.
The interlock enable/disable the motor.
Close: Enable motor Open: Disable motor
J3 Pin 3-5
RS485-1
RS485 Port 1
Modbus Over RS 485 Communication
J4 Pin 1-3
RS485-2
RS485 Port 2
Modbus Over RS 485 Communication
J4 Pin 1, 2
Status
System Fault Status Relay
Relay Contact, Circuit rated at 1A@30VDC or .3A@125VAC
Open: Faulted Close: No Faults
J5 Pin 3,4
Run
Run Relay
Relay Contact, Circuit rated at 1A@30VDC or .3A@125VAC
Open: Speed below configured RPM
Close: Speed above configured RPM
J5 Pin 5,6
EV
EV Relay
Relay contact, circuit rated at:
Max Switching voltage 120VAC
Rated Current : 4amps
Limiting continuous: 3amps
Switching Power: 60W, 62.5VA
Open: Solenoid at rest, Close motor cooling valve
Close: Solenoid active, open motor cooling valve
J6 Pin 1-4
Staging
Staging Valve Driver
Bipolar Step Motor Driver 225 ma max
J6 Pin 6-9
EEV-P
Pressure Regulating Valve
Connect to ETS middle size EEV to control
cold plate temperature
J7 Pin 1-4
Economizer
Combo Sensor
Combo Pressure and Temp
Connects to optional combo sensor for pressure and
temperature measurements Senosr p/n
J7 Pin 5-8
Subcooling
Combo Sensor
Combo Pressure and Temp
Connects to optional combo sensor for pressure and
temperature measurements Senosr p/n
Rev A and B
Connector #
Label
Function
Description
J1
24VDC
CIM Power
24VDC from the CCM to CIM
J2 Pin +/−
Interlock
Drive Interlock
Safety interlock from the Drive, Open when drive is in fault
J2 Pin P/N/GND
Can Bus
CAN Communication
CAN Communication from the drive to the CIM
J3 Pin +/−
Interlock
Interlock
Digital input from PLC without voltage supply.
The interlock enable/disable the motor.
Close: Enable motor Open: Disable motor
J3 Pin GND/A/B
Last Pin Not Used
RS485-1
RS485 Port 1
Modbus Over RS 485 Communication
J4 Pin GND/A/B
Last Pin Not Used
RS485-2
RS485 Port 2
Modbus Over RS 485 Communication
J5 Pin Stat +/−
Status
System Fault
Status Relay
Relay Contact, Circuit rated at 1A@30VDC or .3A@125VAC
Open: Faulted Close: No Faults
J5 Pin Run +/−
Run
Run Relay
Relay Contact, Circuit rated at 1A@30VDC or .3A@125VAC
Open: Speed below configured RPM
Close: Speed above configured RPM
J5 Pin EV +/−
EV
EV Relay
Relay contact, circuit rated at:
Max Switching voltage 120VAC
Rated Current: 4amps
Limiting continuous: 3amps
Switching Power: 60W, 62.5VA
Open: Solenoid at rest, Close motor cooling valve
Close: Solenoid active, open motor cooling valve
J6 Pin
1A/1B/2A/2B
Staging
Staging Valve Driver
Bipolar Step Motor Driver
J6 Pin
1A/1B/2A/2B
EEV-P
Pressure Regulating
Valve
Connect to ETS middle size EEV to control
cold plate temperature
J7 Pin T+/T-/P+/P-
Economizer
Combo Sensor
Combo Pressure
and Temp
Connects to optional combo sensor for pressure and
temperature measurements Senosr p/n
J7 Pin T+/T-/P+/P-
Subcooling
Combo Sensor
Combo Pressure
and Temp
Connects to optional combo sensor for pressure and
temperature measurements Senosr p/n